Skip to main content
Siemens 3VA1225-6FF42-0AA0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1225-6FF42-0AA0 SENTRON MCCB, 125 A, 4-Pole, TM24

MPN3VA1225-6FF42-0AA0
Active

Siemens SENTRON 3VA1225-6FF42-0AA0, molded case circuit breaker, 4-pole, 125 A, TM240 thermal-magnetic trip unit, 220 kA at 240 V AC.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

3VA1225-6FF42-0AA0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
3VA1225-6FF42-0AA0 — Ratings
ParameterValue
Number of poles4
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C250 A
Current at 45 °C250 A
Current at 50 °C250 A
Current at 55 °C243 A
Current at 60 °C237 A
Current at 65 °C230 A
Current at 70 °C223 A
Switching capacity classH
Breaking capacity at 240 V220 kA
Breaking capacity at 415 V154 kA
Breaking capacity at 440 V75.6 kA
Breaking capacity at 500 V30 kA
Breaking capacity at 690 V17 kA
Power loss, max.57 W
3VA1225-6FF42-0AA0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM240
Overcurrent protection functionLI
Ground-fault monitoringWithout
Grounding protection functionNo
3VA1225-6FF42-0AA0 — Construction & Connection
ParameterValue
Main circuit connection typenut keeper kit on both ends
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA1225-6FF42-0AA0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerNo
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts0
3VA1225-6FF42-0AA0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA1225-6FF42-0AA0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.20 000
Height158 mm
Width140 mm
Depth70 mm
Height (in)6.22 in
Width (in)5.51 in
Depth (in)2.76 in

Product details

Its TM240 thermal-magnetic trip unit provides fixed overload and short-circuit protection without undervoltage or ground-fault monitoring — a straightforward fit for main or feeder breaker duty where selectivity coordination is the priority.

Interrupting capacity and selectivity headroom

At 240 V the breaker clears 220 kA, dropping to 154 kA at 415 V, 75.6 kA at 440 V, 30 kA at 500 V, and 17 kA at 690 V.

The breaker carries 250 A through 50 °C ambient, then derates to 243 A at 55 °C, 237 A at 60 °C, 230 A at 65 °C, and 223 A at 70 °C. The 70 mm depth, 140 mm width, and 158 mm height fit standard Siemens SENTRON mounting footprints — verify the existing bus-bar drill pattern if retrofitting into a third-party panel.

Environmental and compliance range

Frequently asked questions

Where can I buy 3VA1225-6FF42-0AA0 and how do I get a price?

This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm quote.

What is the interrupting capacity of 3VA1225-6FF42-0AA0 at 240 V?

At 240 V the breaker clears 220 kA, dropping to 154 kA at 415 V, 75.6 kA at 440 V, 30 kA at 500 V, and 17 kA at 690 V.

What trip unit does 3VA1225-6FF42-0AA0 use?

It uses a TM240 thermal-magnetic trip unit — fixed overload and short-circuit protection, no undervoltage release or ground-fault monitoring.

MPN
3VA1225-6FF42-0AA0