Skip to main content
Siemens 3VA1225-6GF42-0AD0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1225-6GF42-0AD0 SENTRON MCCB, 250 A, 4-Pole, TM24

MPN3VA1225-6GF42-0AD0

Siemens SENTRON 3VA1225-6GF42-0AD0, molded case circuit breaker, 4-pole, 250 A fixed rating, TM240 thermal-magnetic release, line protection design, 70 mm depth, 140 mm width, 158 mm height.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3VA1225-6GF42-0AD0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Basic switch (supplied) ref.3VA12256GF420AA0
Integrated auxiliary / alarm switch ref.3VA9988-0AA12
3VA1225-6GF42-0AD0 — Ratings
ParameterValue
Number of poles4
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C250 A
Current at 45 °C250 A
Current at 50 °C250 A
Current at 55 °C243 A
Current at 60 °C237 A
Current at 65 °C230 A
Current at 70 °C223 A
Switching capacity classH
Breaking capacity at 240 V220 kA
Breaking capacity at 415 V154 kA
Breaking capacity at 440 V75.6 kA
Breaking capacity at 500 V30 kA
Breaking capacity at 690 V17 kA
Power loss, max.57 W
3VA1225-6GF42-0AD0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM240
Overcurrent protection functionLI
Ground-fault monitoringWithout
Grounding protection functionNo
3VA1225-6GF42-0AD0 — Construction & Connection
ParameterValue
Main circuit connection typenut keeper kit on both ends
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA1225-6GF42-0AD0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerNo
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts3
3VA1225-6GF42-0AD0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA1225-6GF42-0AD0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.20 000
Height158 mm
Width140 mm
Depth70 mm
Height (in)6.22 in
Width (in)5.51 in
Depth (in)2.76 in

Product details

The TM240 thermal-magnetic release means it's a fixed-trip unit — no interchangeable trip block — so what you see on the nameplate is what governs the overload and short-circuit protection. Interrupting capacity is where this breaker earns its keep in high-fault installations: 220 kA at 240 V, 154 kA at 415 V, 75.6 kA at 440 V, 30 kA at 500 V, and 17 kA at 690 V. That's a lot of headroom for most commercial and industrial service entrances — you're not going to run out of SCCR on a typical 480 V panel feed. Physical footprint is 70 mm deep by 140 mm wide by 158 mm tall — a standard 4-pole MCCB form factor that drops into SENTRON mounting bases without surprises.

Lifecycle and sourcing — still current, no obsolescence worry

This part carries a current lifecycle stage from Siemens — no phase-out, no last-time-buy notice. It's an active catalog item in the SENTRON 3VA family, so you're not hunting surplus or chasing a replacement.

Integration notes — what fits and what doesn't

The breaker ships with three auxiliary switches (HQ design) integrated, so you get status feedback without adding external contact blocks. If you need those options, you're looking at a different variant in the 3VA family. The 70 mm depth means it fits standard SENTRON mounting plates and busbar systems without clearance issues.

Frequently asked questions

Where can I buy 3VA1225-6GF42-0AD0 and get a price?

This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm number.

What is the interrupting capacity of this MCCB at 480 V?

At 440 V it's rated 75.6 kA; at 500 V it's 30 kA. For a typical 480 V system you'd interpolate between those — still well above what most service entrances need.

Does this breaker include a shunt trip or undervoltage release?

No. This variant has no undervoltage release and no voltage trip. It's a straight thermal-magnetic line-protection breaker with three auxiliary switches.

MPN
3VA1225-6GF42-0AD0