Skip to main content
Siemens 3VA1225-6GF42-0DH0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1225-6GF42-0DH0 SENTRON MCCB, 250 A, 4-Pole, 220

MPN3VA1225-6GF42-0DH0

Siemens SENTRON 3VA1225-6GF42-0DH0, molded case circuit breaker, 4-pole, 250 A rated continuous current, TM240 overcurrent release, 220 kA at 240 V, line protection.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3VA1225-6GF42-0DH0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionLine protection
Integrated auxiliary / alarm switch ref.3VA9988-0AB12
3VA1225-6GF42-0DH0 — Ratings
ParameterValue
Number of poles4
Current at 40 °C250 A
Current at 45 °C250 A
Current at 50 °C250 A
Current at 55 °C243.3 A
Current at 60 °C236.5 A
Current at 65 °C229 A
Current at 70 °C223 A
Switching capacity classH
Breaking capacity at 240 V220 kA
Breaking capacity at 415 V154 kA
Breaking capacity at 440 V36 kA
Breaking capacity at 690 V17 kA
3VA1225-6GF42-0DH0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM240
3VA1225-6GF42-0DH0 — Construction & Connection
ParameterValue
Main circuit connection typelug terminal
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA1225-6GF42-0DH0 — Accessories & Functions
ParameterValue
Undervoltage releaseYes
Voltage triggerNo
Trip indicatorYes
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts3
3VA1225-6GF42-0DH0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA1225-6GF42-0DH0 — Mechanical
ParameterValue
Height158 mm
Width140 mm
Depth70 mm

Product details

Siemens 3VA1225-6GF42-0DH0 — 250 A SENTRON MCCB with TM240 Release

The Siemens 3VA1225-6GF42-0DH0 is a SENTRON molded case circuit breaker (MCCB) rated for 250 A continuous current at 40 °C, with a 4-pole configuration and a TM240 thermal-magnetic overcurrent release. Its interrupting capacity reaches 220 kA at 240 V and 154 kA at 415 V, which means it can safely clear high-fault currents in low-voltage distribution without cascading upstream — a key spec for main or tie-breaker positions where available fault current exceeds 100 kA. For line protection duty, this breaker does not include a voltage trigger, communication module, or phase-failure detection — it is a straightforward overcurrent-only device with an undervoltage release (UVR) fitted as standard. The auxiliary contact block is a 2-auxiliary-switch plus 1-trip-alarm-switch HQ variant (order code 3VA9608-0BB25 for the integrated auxiliary trip). The N-conductor protection is rated at 100 %, so the neutral pole is fully rated for the same current as the phase poles — important for 4-wire distribution where the neutral carries load current.

Above 50 °C the continuous current must be derated per the datasheet curve: 243.3 A at 55 °C, 236.5 A at 60 °C, 229 A at 65 °C, and 223 A at 70 °C.

Dimensions are 158 mm height, 140 mm width, and 70 mm depth. The 70 mm depth means the breaker protrudes less than 3 inches from the mounting surface — relevant when the panel door clearance is tight or when busbar connections are made on the rear.

With a rated insulation voltage of 800 V and interrupting capacities of 36 kA at 440 V and 17 kA at 690 V, this breaker can be applied in 400 V and 690 V systems, though the interrupting rating drops significantly at the higher voltage. For DC network applications, Siemens directs users to the 3VA MCCB device manual for switching power values — the standard AC ratings do not apply in DC circuits.

Frequently asked questions

What is the interrupting capacity of 3VA1225-6GF42-0DH0 at 415 V?

At 415 V, the interrupting capacity is 154 kA. At 240 V it is 220 kA, at 440 V it is 36 kA, and at 690 V it is 17 kA.

What auxiliary contacts come with 3VA1225-6GF42-0DH0?

The breaker is equipped with 2 auxiliary switches plus 1 trip alarm switch (HQ variant). The integrated auxiliary trip order code is 3VA9608-0BB25.

How do I get current pricing and availability for 3VA1225-6GF42-0DH0?

Current pricing and availability are confirmed at quote time. Submit an RFQ for this order code — the part is sourced to order through independent distribution channels.

MPN
3VA1225-6GF42-0DH0