Skip to main content
Siemens 3VA1225-6GF42-0JA0 — Molded Case Circuit Breakers (MCCB)

3VA1225-6GF42-0JA0 Siemens 3VA1 IEC Frame 250, 70kA @ 415V

MPN3VA1225-6GF42-0JA0

Siemens 3VA1 IEC frame 250, breaking capacity class H, Icu=70kA @ 415V, 4-pole, line protection TM240, ATAM, In=250A, overload protection Ir=175A...250A, short-circuit protection Ii=5...10 x In, N conductor protection 100%, nut keeper kit, shunt trip (STL) 110-127V DC, AC 50/60Hz.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Product details

That rating drives the SCCR (short-circuit current rating) for the entire panel downstream, so it is the number the site electrical engineer checks first when coordinating selectivity with the main breaker.

Overload and short-circuit protection settings

The TM240 thermal-magnetic trip unit gives an In=250 A continuous rating. Overload protection (Ir) is adjustable from 175 A to 250 A via the ATAM dial, so a single breaker frame covers a range of feeder sizes — a 200 A motor branch today, a 225 A feeder next quarter. That band lets the panel builder tune coordination with downstream branch breakers without swapping trip units.

Integrated shunt trip and neutral protection

The factory-fitted shunt trip (STL) operates on 110-127 V DC or AC 50/60 Hz — a remote-trip coil for emergency-stop circuits or supervisory control. The N-conductor protection is set at 100%, so the neutral pole tracks the phase poles.

Frequently asked questions

What is the breaking capacity of this breaker?

It is a class H breaker with an Icu of 70 kA at 415 V, which is the maximum short-circuit current it can safely interrupt.

How is the overload protection adjusted on the 3VA1225-6GF42-0JA0?

The TM240 thermal-magnetic trip unit has an adjustable overload protection (Ir) from 175 A to 250 A via the ATAM dial, and the short-circuit magnetic pickup (Ii) is adjustable from 5 to 10 times In.

Where can I buy the 3VA1225-6GF42-0JA0 and how is it quoted?

This part is sourced and quoted to order against an RFQ through independent distribution; availability and current pricing are confirmed at quote time.

MPN
3VA1225-6GF42-0JA0