Skip to main content
Siemens 3VA1225-6GF42-0JH0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1225-6GF42-0JH0 SENTRON MCCB, 250 A, 4-Pole, 220

MPN3VA1225-6GF42-0JH0

Siemens SENTRON 3VA1225-6GF42-0JH0, molded case circuit breaker, 4-pole, 250 A, interrupting rating 220 kA at 240 V AC, line protection design.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

3VA1225-6GF42-0JH0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Basic switch (supplied) ref.3VA12256GF420AA0
Integrated auxiliary / alarm switch ref.3VA9988-0AB12

Ratings

3VA1225-6GF42-0JH0 — Ratings
ParameterValue
Number of poles4
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C250 A
Current at 45 °C250 A
Current at 50 °C250 A
Current at 55 °C243 A
Current at 60 °C237 A
Current at 65 °C230 A
Current at 70 °C223 A
Switching capacity classH
Breaking capacity at 240 V220 kA
Breaking capacity at 415 V154 kA
Breaking capacity at 440 V75.6 kA
Breaking capacity at 500 V30 kA
Breaking capacity at 690 V17 kA
Power loss, max.57 W

Protection & Trip Unit

3VA1225-6GF42-0JH0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM240
Overcurrent protection functionLI
Ground-fault monitoringWithout
Grounding protection functionNo

Construction & Connection

3VA1225-6GF42-0JH0 — Construction & Connection
ParameterValue
Main circuit connection typenut keeper kit on both ends
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40

Accessories & Functions

3VA1225-6GF42-0JH0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerYes
Trip indicatorYes
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts3

Environmental

3VA1225-6GF42-0JH0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C

Mechanical

3VA1225-6GF42-0JH0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.20 000
Height158 mm
Width140 mm
Depth70 mm
Height (in)6.22 in
Width (in)5.51 in
Depth (in)2.76 in

Product details

Siemens 3VA1225-6GF42-0JH0 — 250 A SENTRON MCCB for Line Protection

The Siemens 3VA1225-6GF42-0JH0 is a SENTRON molded case circuit breaker (MCCB) rated 250 A continuous, built for line protection in distribution panels. Four poles handle three-phase plus neutral, with an interrupting capacity of 220 kA at 240 V AC — that drops to 154 kA at 415 V, 75.6 kA at 440 V, 30 kA at 500 V, and 17 kA at 690 V, so the SCCR you can claim downstream depends on the system voltage you feed it. Rated insulation voltage is 800 V, which gives headroom for 690 V systems without derating the dielectric gap. The breaker carries a shunt trip (STL) release and comes with two auxiliary switches plus one trip alarm switch (HQ configuration) — enough for remote status and a separate alarm contact on fault.

Thermal Derating and Panel Fit

At 40 °C through 50 °C the breaker holds its full 250 A rating. Above that it derates: 243 A at 55 °C, 237 A at 60 °C, 230 A at 65 °C, and 223 A at 70 °C. If your panel ambient runs hot — say a sealed enclosure near a furnace line — that 223 A at 70 °C is the number to size against, not the nameplate 250 A. Footprint is 140 mm wide, 158 mm tall, 70 mm deep. That 140 mm width for a 4-pole 250 A frame is standard for SENTRON 3VA — it fits the same DIN-rail or mounting-plate cutout as other 3VA breakers in this frame class. The shunt trip adds a couple of terminals on the left side; plan for wire bending space around it.

Frequently asked questions

What is the interrupting rating of 3VA1225-6GF42-0JH0 at 415 V?

At 415 V the interrupting rating is 154 kA. At 240 V it is 220 kA, and it drops to 75.6 kA at 440 V, 30 kA at 500 V, and 17 kA at 690 V.

Where can I buy 3VA1225-6GF42-0JH0?

This part is sourced and quoted to order against an RFQ through independent distribution channels. Availability and current pricing are confirmed at the time of quote.

What is the thermal derating for 3VA1225-6GF42-0JH0 above 50 °C?

Above 50 °C the breaker derates: 243 A at 55 °C, 237 A at 60 °C, 230 A at 65 °C, and 223 A at 70 °C. Below 50 °C it holds the full 250 A rating.

MPN
3VA1225-6GF42-0JH0