Skip to main content
Siemens 3VA1225-6GF42-0KH0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1225-6GF42-0KH0 SENTRON MCCB, 250 A, 4-Pole, 220

MPN3VA1225-6GF42-0KH0

Siemens SENTRON 3VA1225-6GF42-0KH0, molded case circuit breaker, 4-pole, 250 A, interrupting capacity 220 kA at 240 V AC, line protection design.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

3VA1225-6GF42-0KH0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Basic switch (supplied) ref.3VA12256GF420AA0
Integrated auxiliary / alarm switch ref.3VA9988-0AB12

Ratings

3VA1225-6GF42-0KH0 — Ratings
ParameterValue
Number of poles4
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C250 A
Current at 45 °C250 A
Current at 50 °C250 A
Current at 55 °C243 A
Current at 60 °C237 A
Current at 65 °C230 A
Current at 70 °C223 A
Switching capacity classH
Breaking capacity at 240 V220 kA
Breaking capacity at 415 V154 kA
Breaking capacity at 440 V75.6 kA
Breaking capacity at 500 V30 kA
Breaking capacity at 690 V17 kA
Power loss, max.57 W

Protection & Trip Unit

3VA1225-6GF42-0KH0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM240
Overcurrent protection functionLI
Ground-fault monitoringWithout
Grounding protection functionNo

Construction & Connection

3VA1225-6GF42-0KH0 — Construction & Connection
ParameterValue
Main circuit connection typenut keeper kit on both ends
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40

Accessories & Functions

3VA1225-6GF42-0KH0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerYes
Trip indicatorYes
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts3

Environmental

3VA1225-6GF42-0KH0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C

Mechanical

3VA1225-6GF42-0KH0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.20 000
Height158 mm
Width140 mm
Depth70 mm
Height (in)6.22 in
Width (in)5.51 in
Depth (in)2.76 in

Product details

MCCB for high-fault line protection

The Siemens SENTRON 3VA1225-6GF42-0KH0 is a 4-pole molded case circuit breaker rated 250 A continuous, designed for line protection in distribution panels. Its interrupting capacity hits 220 kA at 240 V, 154 kA at 415 V, and still delivers 17 kA at 690 V — meaning it can clear high-energy faults upstream without cascading to downstream gear. The 800 V rated insulation voltage supports 690 V line-to-line systems with headroom. Thermal derating is minimal up to 50 °C (still 250 A), then drops to 243 A at 55 °C and 223 A at 70 °C. That matters if this breaker sits in a non-climate-controlled enclosure near transformers or drives. The 57 W maximum power loss is the heat you need to vent — factor it into the enclosure sizing calculation.

Auxiliaries and releases

Factory-fitted with 2 auxiliary switches plus 1 trip alarm switch (HQ type) and a shunt trip release (STL). The shunt trip allows remote tripping from an E-stop or safety relay — common for emergency-off circuits. No undervoltage release and no ground-fault monitoring on this variant, so if you need UVR or GF protection, you're looking at a different suffix.

Dimensions and panel fit

Footprint is 140 mm wide × 158 mm tall × 70 mm deep. That's a standard 4-pole MCCB envelope for this current class — mounts on a DIN rail or directly to a backplate via the screw terminals. The 70 mm depth keeps it within typical 200 mm deep enclosure clearance.

Frequently asked questions

Where can I buy 3VA1225-6GF42-0KH0 and how is it quoted?

Sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — no stock or price figures published here.

What is the interrupting capacity of 3VA1225-6GF42-0KH0 at different voltages?

220 kA at 240 V, 154 kA at 415 V, 75.6 kA at 440 V, 30 kA at 500 V, and 17 kA at 690 V (–). The 690 V rating is the one to check for 600 V class systems.

What auxiliaries come fitted on this MCCB?

2 auxiliary switches plus 1 trip alarm switch (HQ type) and a shunt trip release (STL) are factory-installed. No undervoltage release or ground-fault monitoring on this variant.

MPN
3VA1225-6GF42-0KH0