MCCB for high-fault line protection
Its interrupting capacity hits 220 kA at 240 V, 154 kA at 415 V, and still delivers 17 kA at 690 V — meaning it can clear high-energy faults upstream without cascading to downstream gear. Thermal derating is minimal up to 50 °C (still 250 A), then drops to 243 A at 55 °C and 223 A at 70 °C. The 57 W maximum power loss is the heat you need to vent — factor it into the enclosure sizing calculation.
Auxiliaries and releases
The shunt trip allows remote tripping from an E-stop or safety relay — common for emergency-off circuits.
Footprint is 140 mm wide × 158 mm tall × 70 mm deep. The 70 mm depth keeps it within typical 200 mm deep enclosure clearance.