Skip to main content
Siemens 3VA1325-5MH32-0AA0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1325-5MH32-0AA0 SENTRON MCCB, 250 A, 3-Pole

MPN3VA1325-5MH32-0AA0
Active

Siemens SENTRON 3VA1325-5MH32-0AA0, molded case circuit breaker, 3-pole, 250 A rated current at 40 °C, breaking capacity 187 kA at 240 V.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

3VA1325-5MH32-0AA0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
3VA1325-5MH32-0AA0 — Ratings
ParameterValue
Number of poles3
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C250 A
Current at 45 °C250 A
Current at 50 °C250 A
Current at 55 °C245 A
Current at 60 °C239 A
Current at 65 °C234 A
Current at 70 °C228 A
Switching capacity classM
Breaking capacity at 240 V187 kA
Breaking capacity at 415 V121 kA
Breaking capacity at 440 V121 kA
Breaking capacity at 500 V75.6 kA
Breaking capacity at 690 V11.9 kA
Power loss, max.30 W
3VA1325-5MH32-0AA0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM120M
Overcurrent protection functionI
Ground-fault monitoringWithout
Grounding protection functionNo
3VA1325-5MH32-0AA0 — Construction & Connection
ParameterValue
Main circuit connection typenut keeper kit on both ends
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA1325-5MH32-0AA0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerNo
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts0
3VA1325-5MH32-0AA0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA1325-5MH32-0AA0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.20 000
Height248 mm
Width138 mm
Depth110 mm
Height (in)9.76 in
Width (in)5.43 in
Depth (in)4.33 in

Product details

The Siemens 3VA1325-5MH32-0AA0 is a SENTRON molded case circuit breaker (MCCB) rated for 250 A continuous current at 40 °C, with a 3-pole configuration and a thermal-magnetic overcurrent release (TM120M). At 415 V and 440 V the breaking capacity holds at 121 kA; at 500 V it drops to 75.6 kA, and at 690 V it is 11.9 kA.

At 55 °C it derates to 245 A, at 60 °C to 239 A, at 65 °C to 234 A, and at 70 °C to 228 A. In a hot panel near a furnace or drive cabinet, use the 55 °C column for the ampacity budget — the TM120M release is calibrated for the thermal curve, not the ambient. Dimensions are 248 mm high by 138 mm wide by 110 mm deep. Maximum power loss is 30 W.

MPN