What this MCCB delivers
Its interrupting capacity reaches 220 kA at 240 V AC, 154 kA at 415/440 V, 121 kA at 500 V, and 17 kA at 690 V — so it handles high-fault scenarios typical of transformer secondaries and main feeders without cascading upstream. The thermal-magnetic trip unit (TM120M) provides overload and short-circuit protection.
Thermal derating — plan for the panel ambient
At 40 °C and 45 °C the breaker carries the full 250 A. At 55 °C it derates to 245 A, at 60 °C to 239 A, at 65 °C to 234 A, and at 70 °C to 228 A.
The 3-pole design with line and load lugs accepts copper or aluminium conductors sized for 250 A.