What this MCCB does on your line
At 240 V it interrupts 440 kA; at 415 V and 440 V that drops to 242 kA, at 500 V to 154 kA, and at 690 V to 17 kA — so the voltage on your bus decides the fault-clearing headroom you actually have. The thermal derating curve starts at 55 °C: 245 A at 55 °C, 239 A at 60 °C, 234 A at 65 °C, 228 A at 70 °C.
Dimensions are 110 mm deep, 138 mm wide, 248 mm tall — standard SENTRON 3VA footprint for a 250 A frame. Insulation voltage rated at 800 V.