Siemens 3VA1325-5MH32-0AH0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1325-5MH32-0AH0 SENTRON MCCB, 250 A, 3-Pole, 187

MPN3VA1325-5MH32-0AH0

Siemens SENTRON 3VA1325-5MH32-0AH0, molded case circuit breaker, 3-pole, 250 A, breaking capacity 187 kA at 240 V, 121 kA at 415 V, 110 mm depth.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

3VA1325-5MH32-0AH0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Basic switch (supplied) ref.3VA13255MH320AA0
Integrated auxiliary / alarm switch ref.3VA9988-0AB12
3VA1325-5MH32-0AH0 — Ratings
ParameterValue
Number of poles3
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C250 A
Current at 45 °C250 A
Current at 50 °C250 A
Current at 55 °C245 A
Current at 60 °C239 A
Current at 65 °C234 A
Current at 70 °C228 A
Switching capacity classM
Breaking capacity at 240 V187 kA
Breaking capacity at 415 V121 kA
Breaking capacity at 440 V121 kA
Breaking capacity at 500 V75.6 kA
Breaking capacity at 690 V11.9 kA
Power loss, max.30 W
3VA1325-5MH32-0AH0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM120M
Overcurrent protection functionI
Ground-fault monitoringWithout
Grounding protection functionNo
3VA1325-5MH32-0AH0 — Construction & Connection
ParameterValue
Main circuit connection typenut keeper kit on both ends
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA1325-5MH32-0AH0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerNo
Trip indicatorYes
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts3
3VA1325-5MH32-0AH0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA1325-5MH32-0AH0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.20 000
Height248 mm
Width138 mm
Depth110 mm
Height (in)9.76 in
Width (in)5.43 in
Depth (in)4.33 in

Product details

Siemens SENTRON 3VA1325-5MH32-0AH0 — 250 A MCCB with TM120M trip unit

The Siemens SENTRON 3VA1325-5MH32-0AH0 is a 3-pole molded case circuit breaker rated at 250 A continuous, fitted with a TM120M thermal-magnetic overcurrent release. It carries a 187 kA interrupting rating at 240 VAC, stepping down to 121 kA at 415 V and 440 V, 75.6 kA at 500 V, and 11.9 kA at 690 V — the curve tells you where this breaker is comfortable and where it needs upstream coordination. The 250 A frame holds its full rating up to 50 °C ambient; above that it derates linearly to 228 A at 70 °C, which matters if this lands in a hot panel next to drives or transformers.

Mounting and footprint

Dimensions are 248 mm high, 138 mm wide, 110 mm deep — a standard SENTRON 3VA frame size that fits the usual DIN-rail or screw-mount pattern in a distribution panel. Auxiliary switch configuration is 2 aux switches plus 1 trip alarm switch (HQ), already built into the supplied basic switch 3VA13255MH320AA0.

Frequently asked questions

What is the breaking capacity of 3VA1325-5MH32-0AH0 at different voltages?

Rated 187 kA at 240 VAC, 121 kA at 415 V and 440 V, 75.6 kA at 500 V, and 11.9 kA at 690 V — the interrupting rating drops significantly above 500 V, so check coordination if your fault current is high on a 690 V system.

Where can I buy 3VA1325-5MH32-0AH0 and get current pricing?

Sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing confirmed at quote time — submit an RFQ for a firm quote.

MPN