Siemens 3VA1332-6EF32-0DG0 — 320 A SENTRON MCCB with Undervoltage Release
Rated insulation voltage is 800 V, and the thermal current rating holds at 320 A through 50 °C, then derates to 313 A at 55 °C, 306 A at 60 °C, 299 A at 65 °C, and 292 A at 70 °C. That derating curve is the one to check if the breaker sits near other heat sources in a packed enclosure.
That 110 mm depth is the dimension to watch when the breaker mounts in a shallow backpanel or against a gland plate — it fits standard SENTRON 3VA drawout and fixed-mount footprints, so a panel kitted for a 3VA frame will accept this unit without re-drilling.