Skip to main content
Siemens 3VA1340-4EF32-0AF0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1340-4EF32-0AF0 SENTRON MCCB, 400 A, 3-Pole, Line

MPN3VA1340-4EF32-0AF0

Siemens SENTRON 3VA1340-4EF32-0AF0, molded case circuit breaker, 3-pole, 400 A (at 40 °C), line protection version with TM240 overcurrent release, 121 kA breaking capacity at 240 V.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3VA1340-4EF32-0AF0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionLine protection
Basic switch (supplied) ref.3VA13404EF320AA0
Integrated auxiliary / alarm switch ref.3VA9988-0AB12
3VA1340-4EF32-0AF0 — Ratings
ParameterValue
Number of poles3
Current at 40 °C400 A
Current at 45 °C400 A
Current at 50 °C400 A
Current at 55 °C392 A
Current at 60 °C384 A
Current at 65 °C376 A
Current at 70 °C367 A
Switching capacity classS
Breaking capacity at 240 V121 kA
Breaking capacity at 415 V76 kA
Breaking capacity at 440 V76 kA
Breaking capacity at 500 V53 kA
Breaking capacity at 690 V10.5 kA
Power loss, max.92.1 W
3VA1340-4EF32-0AF0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM240
Overcurrent protection functionLI
Ground-fault monitoringWithout
3VA1340-4EF32-0AF0 — Construction & Connection
ParameterValue
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA1340-4EF32-0AF0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerNo
Trip indicatorYes
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts2
3VA1340-4EF32-0AF0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA1340-4EF32-0AF0 — Mechanical
ParameterValue
Height248 mm
Width138 mm
Depth110 mm
Height (in)9.8 in
Width (in)5.4 in
Depth (in)4.3 in

Product details

What it is and what it does

The Siemens 3VA1340-4EF32-0AF0 is a SENTRON molded case circuit breaker (MCCB) rated for line protection, meaning its primary job is to protect cables and busbars from overloads and short circuits in a distribution panel — not motor protection, which requires a different trip curve. It carries a continuous current rating of 400 A at 40 °C, and that figure holds steady up to 50 °C before derating begins — at 55 °C it's still good for 392 A, at 70 °C it drops to 367 A, so the thermal margin is generous for most panel environments. The TM240 overcurrent release is a thermal-magnetic type — the thermal element handles overloads, the magnetic element handles short circuits — tuned for line protection duty, not motor starting.

Breaking capacity — what the ratings mean for your fault level

Breaking capacity is the maximum fault current the breaker can safely interrupt without welding contacts or rupturing the case. This MCCB delivers 121 kA at 240 V, 76 kA at 415 V and 440 V, 53 kA at 500 V, and 10.5 kA at 690 V — so it handles high available fault currents at the lower voltages common in North American and some European distribution, while the 690 V figure still covers most industrial service-entrance requirements. Rated insulation voltage is 800 V, which means the internal clearances and creepage distances are designed for systems up to that level — the 690 V breaking capacity is the practical limit for a fault interruption, but the insulation path is rated higher.

Lifecycle and sourcing reality

The auxiliary contact configuration is 1 auxiliary switch + 1 trip alarm switch (HQ version), which gives you both a status mirror and a separate alarm contact for remote fault indication — useful for PLC or SCADA integration without adding external relays. Power loss at rated current is 92.1 W maximum — factor that into your panel thermal budget, especially if the breaker is enclosed or mounted in a densely packed switchboard.

Panel fit and integration

Dimensions are 248 mm high, 138 mm wide, 110 mm deep. Depth of 110 mm fits most enclosures with room for rear cable access. Operating temperature range is -25 °C to 70 °C, storage from -40 °C to 80 °C.

MPN