The Siemens SENTRON 3VA1340-4EF32-0DE0 is a 3-pole molded case circuit breaker rated for continuous 400 A at 40 °C, with a 121 kA interrupting capacity at 240 V.
Breaking capacity across voltage
This MCCB delivers 75.6 kA at 415 V and 440 V, 52.5 kA at 500 V, and 11.9 kA at 690 V. The steep drop above 500 V means it's best suited for 240–480 V systems where the SCCR headroom is generous.
Integration and accessories
No communication function onboard — this is a standalone line protection breaker, not a smart metering device.