Overload and short-circuit settings
The TM240 ATAM trip unit gives you an adjustable overload protection range Ir=280 A to 400 A (the In=400 A rating), so you dial in the exact continuous current for your load — a 300 A feeder gets Ir=300 A, not a fixed value. Short-circuit protection Ii is adjustable from 5 to 10 times In, meaning 2000 A to 4000 A magnetic pickup.