Rated current and breaking capacity
Breaking capacity reaches 220 kA at 240 V AC, 154 kA at 415 V and 440 V, 121 kA at 500 V, and 17 kA at 690 V — figures that cover most industrial distribution panels and motor control centers.
Integrated undervoltage release and auxiliary switches
Maximum power loss 92.1 W at rated load, which drives enclosure ventilation requirements.