Skip to main content
Siemens 3VA1450-1AA42-0AA0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1450-1AA42-0AA0 SENTRON Switch Disconnector, 500

MPN3VA1450-1AA42-0AA0
Active

Siemens SENTRON 3VA1450-1AA42-0AA0, switch disconnector in MCCB design, 4-pole, rated current 500 A, AC 690 V / DC 600 V, without overload or short-circuit protection, busbar connection.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

3VA1450-1AA42-0AA0 — Identification
ParameterValue
Product designationSwitch disconnector
Brand / rangeSENTRON
3VA1450-1AA42-0AA0 — Ratings
ParameterValue
Number of poles4
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C500 A
Current at 45 °C500 A
Current at 50 °C500 A
Current at 55 °C500 A
Current at 60 °C500 A
Current at 65 °C500 A
Current at 70 °C500 A
Power loss, max.120 W
3VA1450-1AA42-0AA0 — Construction & Connection
ParameterValue
Main circuit connection typebusbar connection
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA1450-1AA42-0AA0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerNo
Trip indicatorNo
Motor drive optionYes
Auxiliary CO contacts0
3VA1450-1AA42-0AA0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA1450-1AA42-0AA0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.15 000
Height248 mm
Width184 mm
Depth110 mm

Product details

It is designed as a main isolating device for load centres, distribution boards, or machine infeed sections where the upstream protection (a separate MCCB or fuse) already handles fault clearing. Rated for AC 690 V and DC 600 V, it covers most industrial supply voltages short of medium-voltage gear. It connects via busbar or front-terminal main current connections, which suits panel layouts where the disconnect bolts directly to a bus riser rather than landing on cables.

The 3VA1450-1AA42-0AA0 measures 248 mm high, 184 mm wide, and 110 mm deep. It mounts in the standard MCCB cutout footprint for the 3VA1 frame, so if you are replacing a 3VA1 or similar-frame SENTRON disconnect, the panel cutout and busbar centres carry over without rework. IP40 on the front keeps dust and tools out; the rear and sides are open to the enclosure, so the panel itself provides the IP rating. The disconnect ships with a nut-keeper kit for busbar mounting. No auxiliary contacts, no undervoltage release, and no communication function are fitted on this variant, so it is a pure mechanical isolator. If you need a shunt trip or aux switch later, the product extension option for a motor drive is listed as available, but the auxiliary release design is specified as 'without' on this order code.

Typical mechanical service life is 15,000 operating cycles. Maximum power loss is 120 W at rated current.

Frequently asked questions

Does the 3VA1450-1AA42-0AA0 include overload or short-circuit protection?

No — it is a switch disconnector only, specified without overload protection and without short-circuit protection. It functions as a load-break isolating switch and requires upstream protection (MCCB or fuses) for fault clearing.

What panel dimensions does 3VA1450-1AA42-0AA0 require?

Height 248 mm, width 184 mm, depth 110 mm. It fits the standard 3VA1 frame MCCB cutout.

MPN