At 45 °C and 50 °C it still holds 500 A; above that it steps down to 488 A at 55 °C, 476 A at 60 °C, 464 A at 65 °C, and 452 A at 70 °C. Interrupting capacity is 121 kA at 240 V, 75.6 kA at 415 V and 440 V, 52.5 kA at 500 V, and 11.9 kA at 690 V. It mounts in a panel with a 184 mm width, 248 mm height, and 110 mm depth. Front protection is IP40.
Panel integration: the 184 mm width and 110 mm depth fit a standard MCCB cutout. If the BOM calls for aux contacts or remote trip, you need the accessory kit separately.