Skip to main content
Siemens 3VA1450-7EF32-0KE0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1450-7EF32-0KE0 SENTRON MCCB, 500 A, 440 kA at 24

MPN3VA1450-7EF32-0KE0

Siemens SENTRON 3VA1, molded case circuit breaker, 3-pole, 500 A at 40 °C, 440 kA at 240 VAC, line protection, 110 mm depth, 138 mm width, 248 mm height.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3VA1450-7EF32-0KE0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Basic switch (supplied) ref.3VA14507EF320AA0
Integrated auxiliary / alarm switch ref.3VA9988-0AA12
3VA1450-7EF32-0KE0 — Ratings
ParameterValue
Number of poles3
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C500 A
Current at 45 °C500 A
Current at 50 °C500 A
Current at 55 °C488 A
Current at 60 °C476 A
Current at 65 °C464 A
Current at 70 °C452 A
Switching capacity classC
Breaking capacity at 240 V440 kA
Breaking capacity at 415 V242 kA
Breaking capacity at 440 V242 kA
Breaking capacity at 500 V154 kA
Breaking capacity at 690 V17 kA
Power loss, max.122.7 W
3VA1450-7EF32-0KE0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM240
Overcurrent protection functionLI
Ground-fault monitoringWithout
Grounding protection functionNo
3VA1450-7EF32-0KE0 — Construction & Connection
ParameterValue
Main circuit connection typenut keeper kit on both ends
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA1450-7EF32-0KE0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerYes
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts4
3VA1450-7EF32-0KE0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA1450-7EF32-0KE0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.20 000
Height248 mm
Width138 mm
Depth110 mm
Height (in)9.76 in
Width (in)5.43 in
Depth (in)4.33 in

Product details

What this 500 A MCCB delivers — and where the rating matters

It carries 500 A continuously at 40 °C without derating, and holds that same 500 A rating through 50 °C — at 55 °C it still delivers 488 A, at 70 °C it delivers 452 A. That thermal curve matters if this breaker lands in a non-climate-controlled enclosure or a panel near process heat. The interrupting rating is the headline number: 440 kA at 240 VAC. At 415 V and 440 V it interrupts 242 kA; at 500 V it handles 154 kA; at 690 V it still clears 17 kA. That is not a typo — this is a high-breaking-capacity frame sized for large fault-current duty where a standard MCCB would fail to clear and cascade upstream.

Three-pole construction, 138 mm wide, 248 mm tall, 110 mm deep. The auxiliary switch block accommodates 4 HQ auxiliary switches; the shunt trip (STL) auxiliary release is included for remote tripping.

Frequently asked questions

What is the breaking capacity of this MCCB at 240 V?

440 kA at 240 VAC. At 415 V and 440 V it is 242 kA; at 500 V it is 154 kA; at 690 V it is 17 kA.

Where can I buy 3VA1450-7EF32-0KE0?

Sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time.

MPN
3VA1450-7EF32-0KE0