Skip to main content
Siemens 3VA1463-4EE32-0AA0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1463-4EE32-0AA0 SENTRON MCCB, 630 A, 3-Pole, TM22

MPN3VA1463-4EE32-0AA0

Siemens SENTRON 3VA1463-4EE32-0AA0, molded case circuit breaker, 3-pole, 630 A, TM220 overcurrent release, line protection design, 110 mm depth, 138 mm width, 248 mm height.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

3VA1463-4EE32-0AA0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
3VA1463-4EE32-0AA0 — Ratings
ParameterValue
Number of poles3
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C630 A
Current at 45 °C630 A
Current at 50 °C630 A
Current at 55 °C618 A
Current at 60 °C607 A
Current at 65 °C595 A
Current at 70 °C583 A
Switching capacity classS
Breaking capacity at 240 V121 kA
Breaking capacity at 415 V75.6 kA
Breaking capacity at 440 V75.6 kA
Breaking capacity at 500 V52.5 kA
Breaking capacity at 690 V11.9 kA
Power loss, max.192.9 W
3VA1463-4EE32-0AA0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM220
Overcurrent protection functionLI
Ground-fault monitoringWithout
Grounding protection functionNo
3VA1463-4EE32-0AA0 — Construction & Connection
ParameterValue
Main circuit connection typenut keeper kit on both ends
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA1463-4EE32-0AA0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerNo
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts0
3VA1463-4EE32-0AA0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA1463-4EE32-0AA0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.20 000
Height248 mm
Width138 mm
Depth110 mm
Height (in)9.76 in
Width (in)5.43 in
Depth (in)4.33 in

Product details

That current holds flat through 50 °C; at 55 °C it derates to 618 A, at 60 °C to 607 A, at 65 °C to 595 A, and at 70 °C to 583 A — so in a warm panel you still have headroom down to about 580 A. The TM220 overcurrent release gives it a thermal-magnetic trip curve with fixed thermal and magnetic settings, which means no field-adjustable dials — you select the frame for the load and it protects. Breaking capacity runs 121 kA at 240 V, 75.6 kA at 415 V and 440 V, 52.5 kA at 500 V, and 11.9 kA at 690 V, so it handles high-fault utility feeds and large motor branch circuits.

Frequently asked questions

How do I get current pricing and availability for 3VA1463-4EE32-0AA0?

Submit an RFQ through this listing. Availability and current pricing are confirmed at quote time through our independent distribution channels.

What are the key ratings for 3VA1463-4EE32-0AA0?

Rated 630 A at 40 °C, 3-pole, TM220 thermal-magnetic release, breaking capacity 121 kA at 240 V and 75.6 kA at 415 V. Dimensions 248 x 138 x 110 mm.

What compliance documentation does this brand provide for 3VA1463-4EE32-0AA0?

As a Siemens SENTRON series MCCB, it carries the standard manufacturer declarations — RoHS, REACH, and applicable IEC/UL certifications. Specific certificates are available on request with the RFQ.

MPN
3VA1463-4EE32-0AA0