The continuous current rating is 630 A at 40 °C, and it holds that same 630 A through 50 °C; at 55 °C it derates to 618 A, at 60 °C to 607 A, at 65 °C to 595 A, and at 70 °C to 583 A. The interrupting ratings are what decide whether this breaker clears a fault without upstream damage: 121 kA at 240 V, 75.6 kA at 415 V and 440 V, 52.5 kA at 500 V, and 11.9 kA at 690 V. The 3-pole form factor (138 mm wide, 248 mm tall, 110 mm deep) fits the standard SENTRON 3VA mounting footprint; it carries a built-in undervoltage release (UVR) and one auxiliary switch plus one trip alarm switch, which covers the basic status feedback to a PLC or annunciator.
Siemens 3VA1463-4EF32-0DF0 SENTRON MCCB, 630A, 3-Pole, 121kA
Siemens SENTRON 3VA1463-4EF32-0DF0, molded case circuit breaker, 3-pole, 630 A at 40 °C, breaking capacity 121 kA at 240 V AC, line protection design, with undervoltage release.
Specifications
| Parameter | Value |
|---|---|
| Product designation | Molded case circuit breaker |
| Brand / range | SENTRON |
| Basic switch (supplied) ref. | 3VA14634EF320AA0 |
| Integrated auxiliary / alarm switch ref. | 3VA9988-0AB12 |
| Parameter | Value |
|---|---|
| Number of poles | 3 |
| Rated operational voltage Ue (AC) | 690 V |
| Rated insulation voltage Ui | 800 V |
| Current at 40 °C | 630 A |
| Current at 45 °C | 630 A |
| Current at 50 °C | 630 A |
| Current at 55 °C | 618 A |
| Current at 60 °C | 607 A |
| Current at 65 °C | 595 A |
| Current at 70 °C | 583 A |
| Switching capacity class | S |
| Breaking capacity at 240 V | 121 kA |
| Breaking capacity at 415 V | 75.6 kA |
| Breaking capacity at 440 V | 75.6 kA |
| Breaking capacity at 500 V | 52.5 kA |
| Breaking capacity at 690 V | 11.9 kA |
| Power loss, max. | 195.4 W |
| Parameter | Value |
|---|---|
| Overcurrent release (trip unit) type | TM240 |
| Overcurrent protection function | LI |
| Ground-fault monitoring | Without |
| Grounding protection function | No |
| Parameter | Value |
|---|---|
| Main circuit connection type | nut keeper kit on both ends |
| Main circuit connector arrangement | Front terminal |
| Protection class (IP), front | IP40 |
| Parameter | Value |
|---|---|
| Undervoltage release | Yes |
| Voltage trigger | No |
| Trip indicator | Yes |
| Communication function | No |
| Measurement function | No |
| Motor drive option | Yes |
| Auxiliary CO contacts | 2 |
| Parameter | Value |
|---|---|
| Operating temperature, max. | 70 °C |
| Operating temperature, min. | -25 °C |
| Storage temperature, max. | 80 °C |
| Storage temperature, min. | -40 °C |
| Parameter | Value |
|---|---|
| Mechanical service life (operating cycles), typ. | 20 000 |
| Height | 248 mm |
| Width | 138 mm |
| Depth | 110 mm |
| Height (in) | 9.76 in |
| Width (in) | 5.43 in |
| Depth (in) | 4.33 in |
Product details
Frequently asked questions
Where can I buy 3VA1463-4EF32-0DF0 and how do I get a price?
This part is sourced and quoted to order against an RFQ through independent distribution. Submit an RFQ for current pricing and availability — no stock count or price is published here.
What are the key ratings of 3VA1463-4EF32-0DF0?
Rated 630 A continuous at 40 °C, 3-pole, with breaking capacities of 121 kA at 240 V, 75.6 kA at 415 V, 75.6 kA at 440 V, 52.5 kA at 500 V, and 11.9 kA at 690 V. It includes an undervoltage release and one auxiliary + one trip alarm switch.
What is the depth of 3VA1463-4EF32-0DF0?
The depth is 110 mm (4.33 in). Combined with the 138 mm width and 248 mm height, it fits the standard 3VA mounting footprint.
What compliance documentation does Siemens provide for this MCCB?
As a SENTRON 3VA series MCCB, this part carries the usual Siemens compliance documentation — RoHS, REACH, UL, and IEC declarations are available from Siemens directly. Specific cert numbers are not listed in this record.