630 A MCCB with Undervoltage Release — Panel Integration Notes
The Siemens 3VA1463-4EF42-0DA0 is a SENTRON molded case circuit breaker rated for 630 A continuous at 40 °C through 50 °C, derating to 583 A at 70 °C. Its 121 kA breaking capacity at 240 V AC (75.6 kA at 415 V, 52.5 kA at 500 V, 11.9 kA at 690 V) gives it the headroom for high-fault service-entrance or distribution applications where the available fault current is stiff.
The TM240 overcurrent release (thermal-magnetic, fixed at 240 A trip) is the internal trip unit; verify that the trip setting matches your load's full-load current and cable ampacity.