Skip to main content
Siemens 3VA1463-4FF42-0AA0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1463-4FF42-0AA0 SENTRON MCCB, 315 A, 4-Pole, TM24

MPN3VA1463-4FF42-0AA0
Active

Siemens SENTRON 3VA1463-4FF42-0AA0, molded case circuit breaker (MCCB), 4-pole, 315 A fixed, TM240 thermal-magnetic trip unit, line protection design, IP40 front.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3VA1463-4FF42-0AA0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
3VA1463-4FF42-0AA0 — Ratings
ParameterValue
Number of poles4
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C630 A
Current at 45 °C630 A
Current at 50 °C630 A
Current at 55 °C618 A
Current at 60 °C607 A
Current at 65 °C595 A
Current at 70 °C583 A
Switching capacity classS
Breaking capacity at 240 V121 kA
Breaking capacity at 415 V75.6 kA
Breaking capacity at 440 V75.6 kA
Breaking capacity at 500 V52.5 kA
Breaking capacity at 690 V11.9 kA
Power loss, max.192.9 W
3VA1463-4FF42-0AA0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM240
Overcurrent protection functionLI
Ground-fault monitoringWithout
Grounding protection functionNo
3VA1463-4FF42-0AA0 — Construction & Connection
ParameterValue
Main circuit connection typenut keeper kit on both ends
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA1463-4FF42-0AA0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerNo
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts0
3VA1463-4FF42-0AA0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA1463-4FF42-0AA0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.20 000
Height248 mm
Width184 mm
Depth110 mm
Height (in)9.76 in
Width (in)7.24 in
Depth (in)4.33 in

Product details

For a panel builder, the fixed rating eliminates field-adjustment errors: what you order is what protects the feeder. At 240 V it interrupts 121 kA; at 415 V it holds 75.6 kA; at 690 V it still clears 11.9 kA. Thermal derating is published across the full operating range: full 630 A capability up to 50 °C, then a gentle slope to 583 A at 70 °C. That means in a crowded, warm enclosure — say a MCC bucket with other breakers — you don't lose headroom until the ambient passes 50 °C. The 192.9 W maximum power loss matters for ventilation planning in sealed cabinets.

Dimensions are 248 mm high, 184 mm wide, 110 mm deep — a standard 4-pole MCCB footprint for 630 A frame. The 184 mm width means it occupies roughly 7.24 inches of DIN-rail or mounting-plate space. IP40 on the front face is typical for switchboard installation; no washdown rating, so keep this inside a dry enclosure.

MPN
3VA1463-4FF42-0AA0