Skip to main content
Siemens 3VA1463-4GF42-0AF0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1463-4GF42-0AF0 Circuit Breaker, 630A, 36kA @ 415

MPN3VA1463-4GF42-0AF0

Siemens 3VA1 series, IEC frame 630 circuit breaker, breaking capacity class S, 4-pole, In=630A, Icu=36kA @ 415V, TM240, ATAM, with auxiliary switch and trip alarm.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Product details

The Siemens 3VA1463-4GF42-0AF0 is a 4-pole IEC frame 630 circuit breaker from the 3VA1 series, rated for line protection with a TM240 thermal-magnetic trip unit.

Overload and short-circuit protection settings

The thermal overload protection Ir is adjustable from 440 A to 630 A, matching the full In=630 A rating. The magnetic short-circuit pickup Ii is set at 4 to 8 times In, so on a 630 A frame that gives a pickup range of 2520 A to 5040 A — wide enough to ride through motor inrush on a large pump or compressor feeder while still clearing a bolted fault fast.

Integrated accessories

That means you get a position-feedback contact for the panel PLC and a separate alarm contact that changes state only when the breaker trips on fault — no need to order and mount them separately in the field.

Frequently asked questions

Where can I buy 3VA1463-4GF42-0AF0 and get a price?

This part is sourced and quoted to order against an RFQ through independent distribution. Submit an RFQ for current pricing and availability — confirmed at quote time.

What is the breaking capacity of this breaker?

The breaking capacity class S gives Icu=36kA at 415 V, meaning it can safely interrupt fault currents up to 36 kA on a 415 VAC system.

What accessories are included with this order code?

This order code includes one auxiliary switch (changeover H) and one trip alarm switch (changeover), both factory-fitted.

MPN
3VA1463-4GF42-0AF0