Skip to main content
Siemens 3VA1463-5EF42-0AA0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1463-5EF42-0AA0 SENTRON MCCB, 630 A, 4-Pole, TM24

MPN3VA1463-5EF42-0AA0
Active

Siemens SENTRON 3VA1463-5EF42-0AA0, molded case circuit breaker, 4-pole, 630 A at 40 °C, TM240 thermal-magnetic trip, 187 kA at 240 V.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

3VA1463-5EF42-0AA0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionLine protection

Ratings

3VA1463-5EF42-0AA0 — Ratings
ParameterValue
Number of poles4
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C630 A
Current at 45 °C630 A
Current at 50 °C630 A
Current at 55 °C618 A
Current at 60 °C607 A
Current at 65 °C595 A
Current at 70 °C583 A
Switching capacity classM
Breaking capacity at 240 V187 kA
Breaking capacity at 415 V121 kA
Breaking capacity at 440 V121 kA
Breaking capacity at 500 V75.6 kA
Breaking capacity at 690 V11.9 kA
Power loss, max.192.9 W

Protection & Trip Unit

3VA1463-5EF42-0AA0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM240
Overcurrent protection functionLI
Ground-fault monitoringWithout

Construction & Connection

3VA1463-5EF42-0AA0 — Construction & Connection
ParameterValue
Main circuit connection typenut keeper kit on both ends
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40

Accessories & Functions

3VA1463-5EF42-0AA0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerNo
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts0

Environmental

3VA1463-5EF42-0AA0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C

Mechanical

3VA1463-5EF42-0AA0 — Mechanical
ParameterValue
Height248 mm
Width184 mm
Depth110 mm
Height (in)9.76 in
Width (in)7.24 in
Depth (in)4.33 in

Product details

630 A MCCB with 187 kA interrupting capacity

The Siemens SENTRON 3VA1463-5EF42-0AA0 is a 4-pole molded case circuit breaker rated for 630 A continuous at 40 °C, with a TM240 thermal-magnetic trip unit designed for line protection. Its interrupting capacity hits 187 kA at 240 V and 121 kA at 415 V, which means it can clear high-fault currents in a main distribution panel without cascading upstream — critical for selectivity in a multi-level installation.

Current derating and thermal management

At 40 °C, 45 °C, and 50 °C the breaker holds 630 A without derating. Above that, it drops to 618 A at 55 °C, 607 A at 60 °C, 595 A at 65 °C, and 583 A at 70 °C. The maximum power loss is 192.9 W — a figure to check against enclosure ventilation, especially when ganging multiple breakers in a compact panel.

Physical footprint and panel fit

Dimensions are 184 mm wide, 248 mm tall, and 110 mm deep — a standard SENTRON 3VA frame size for this current class. Front protection is IP40, so it's suited for a dry indoor enclosure but not washdown areas.

Frequently asked questions

What trip unit does the 3VA1463-5EF42-0AA0 use?

It uses a TM240 thermal-magnetic trip unit, which is adjustable for the I²t curve, designed for line protection applications.

MPN