Undervoltage release (UVR) is built in. Breaking capacity: 187 kA at 240 V, 121 kA at 415 V and 440 V, 75.6 kA at 500 V, 52.5 kA at 690 V. That covers most industrial distribution panels up to 690 V with headroom for high-fault service entrances.
Full 1000 A rating holds through 50 °C. At 55 °C it's 960 A; at 60 °C, 940 A; at 65 °C, 920 A; at 70 °C, 900 A. Dimensions: 320 mm high × 210 mm wide × 120 mm deep. That's a 3-pole MCCB in a standard SENTRON 3VA footprint — no oddball cutout.