It carries a 1000 A frame at 40 °C, 3-pole, with a short-circuit breaking capacity of 187 kA at 240 V — that rating means it clears a fault at that level without upstream damage, critical for high-fault utility feeds. The interrupting curve drops to 121 kA at 415/440 V and 75.6 kA at 500 V, so the installed SCCR must be coordinated with the available fault current at the point of common coupling.
Lifecycle status is current — this is an active catalog number, not a phase-out or last-time-buy.
Panel footprint: 210 mm wide, 320 mm tall, 120 mm deep. The 3-pole body accepts line- and load-side lugs for copper or aluminum conductors.
Thermal derating: the 1000 A rating holds through 50 °C ambient. Above that, it steps down — 960 A at 55 °C, 940 A at 60 °C, 920 A at 65 °C, 900 A at 70 °C. For a panel with internal temperature rise, size the continuous load against the derated value at the actual enclosure ambient, not the nameplate 1000 A. Maximum power loss is 332.5 W, which must be factored into the enclosure ventilation calculation.