Rated current and breaking capacity
It carries a continuous current of 1 000 A at 40 °C, derating to 900 A at 70 °C — a thermal curve that governs the actual load it can handle in a warm panel. Breaking capacity reaches 187 kA at 240 V AC, 121 kA at 415 V, and 52.5 kA at 690 V, giving you selectivity headroom for high-fault installations.
Built-in undervoltage release
No separate undervoltage module to mount or wire.
Footprint: 210 mm wide × 320 mm tall × 120 mm deep. The 210 mm width is the critical dimension for DIN-rail or backplate layout — verify busbar spacing and enclosure gland-plate clearance before committing the cutout. Power loss is 332.5 W maximum, so forced ventilation or derating may be needed in a sealed enclosure.