Thermal derating and power dissipation
Above that, derate linearly: 960 A at 55 °C, 940 A at 60 °C, 920 A at 65 °C, and 900 A at 70 °C. Maximum power loss is 332.5 W, which factors into enclosure ventilation sizing.
Built-in undervoltage release, auxiliary switches
No ground-fault monitoring version is included; that's a separate variant if you need it.
Dimensions are 320 mm high, 210 mm wide, 120 mm deep — a substantial frame for the 1000 A rating. No communication function on this variant, no voltage trigger, no trip indicator.