Siemens 3VA1580-5EF32-0AC0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1580-5EF32-0AC0 SENTRON MCCB, 800 A, 3-Pole, Line

MPN3VA1580-5EF32-0AC0

Siemens SENTRON 3VA1580-5EF32-0AC0, molded case circuit breaker, 3-pole, 800 A rated current (40-50 °C), 187 kA breaking capacity at 240 V, TM240 release, line protection design.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

3VA1580-5EF32-0AC0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Basic switch (supplied) ref.3VA15805EF320AA0
Integrated auxiliary / alarm switch ref.3VA9988-0AA12
3VA1580-5EF32-0AC0 — Ratings
ParameterValue
Number of poles3
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C800 A
Current at 45 °C800 A
Current at 50 °C800 A
Current at 55 °C780 A
Current at 60 °C761 A
Current at 65 °C741 A
Current at 70 °C722 A
Switching capacity classM
Breaking capacity at 240 V187 kA
Breaking capacity at 415 V121 kA
Breaking capacity at 440 V121 kA
Breaking capacity at 500 V75.6 kA
Breaking capacity at 690 V52.5 kA
Power loss, max.240 W
3VA1580-5EF32-0AC0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM240
Overcurrent protection functionLI
Ground-fault monitoringWithout
Grounding protection functionNo
3VA1580-5EF32-0AC0 — Construction & Connection
ParameterValue
Main circuit connection typenut keeper kit on both ends
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA1580-5EF32-0AC0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerNo
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionNo
Auxiliary CO contacts2
3VA1580-5EF32-0AC0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA1580-5EF32-0AC0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.10 000
Height320 mm
Width210 mm
Depth120 mm
Height (in)12.6 in
Width (in)8.27 in
Depth (in)4.72 in

Product details

What it is and what it does

The Siemens 3VA1580-5EF32-0AC0 is a SENTRON molded case circuit breaker (MCCB) designed for line protection in distribution panels. It carries a continuous current rating of 800 A at ambient temperatures up to 50 °C, derating to 722 A at 70 °C — so in a warm enclosure you lose about 10% of the headroom. The TM240 thermal-magnetic release handles overload and short-circuit protection without external trip units. Breaking capacity is 187 kA at 240 V AC, 121 kA at 415/440 V, and 52.5 kA at 690 V — that's a high-interrupting rating for a 3-pole frame, meaning it can clear severe faults without upstream fuses in most low-voltage industrial feeds.

Panel fit and integration

The breaker measures 320 mm high, 210 mm wide, and 120 mm deep — a standard SENTRON 3VA frame size. It mounts on a DIN rail or directly to a backplate; the 3-pole block leaves room for auxiliary switches (2 HQ contacts included) and shunt trips if needed. Rated insulation voltage is 800 V, so it's comfortable on 690 V systems with margin. Power loss at full load is 240 W maximum — account for that heat in the enclosure sizing, especially if you're stacking multiple breakers in a sealed cabinet.

Frequently asked questions

How do I get current pricing and availability for 3VA1580-5EF32-0AC0?

Submit an RFQ through this listing. The part is sourced to order via independent distribution; current pricing and stock levels are confirmed at quote time.

What is 3VA1580-5EF32-0AC0's depth?

The depth is 120 mm (4.72 in).

What is 3VA1580-5EF32-0AC0's width?

The width is 210 mm (8.27 in).

Will 3VA1580-5EF32-0AC0 drop into a panel specified around 3VA1110-5ED36-0AC0 without rewiring?

No — the 3VA1580 is an 800 A frame (320x210x120 mm) with a TM240 release, while the 3VA1110 series is a smaller 100-160 A frame. The cutout dimensions, busbar spacing, and lug sizes differ; a panel designed for the 3VA1110 cannot physically accept the 3VA1580 without rework.

MPN
3VA1580-5EF32-0AC0