Siemens 3VA1580-5EF32-0AH0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1580-5EF32-0AH0 SENTRON MCCB, 800 A, 187 kA

MPN3VA1580-5EF32-0AH0

Siemens SENTRON 3VA1580-5EF32-0AH0, molded case circuit breaker, 3-pole, 800 A at 40 °C, breaking capacity 187 kA at 240 V AC, TM240 release, line protection.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

3VA1580-5EF32-0AH0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Basic switch (supplied) ref.3VA15805EF320AA0
Integrated auxiliary / alarm switch ref.3VA9988-0AB12
3VA1580-5EF32-0AH0 — Ratings
ParameterValue
Number of poles3
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C800 A
Current at 45 °C800 A
Current at 50 °C800 A
Current at 55 °C780 A
Current at 60 °C761 A
Current at 65 °C741 A
Current at 70 °C722 A
Switching capacity classM
Breaking capacity at 240 V187 kA
Breaking capacity at 415 V121 kA
Breaking capacity at 440 V121 kA
Breaking capacity at 500 V75.6 kA
Breaking capacity at 690 V52.5 kA
Power loss, max.240 W
3VA1580-5EF32-0AH0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM240
Overcurrent protection functionLI
Ground-fault monitoringWithout
Grounding protection functionNo
3VA1580-5EF32-0AH0 — Construction & Connection
ParameterValue
Main circuit connection typenut keeper kit on both ends
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA1580-5EF32-0AH0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerNo
Trip indicatorYes
Communication functionNo
Measurement functionNo
Motor drive optionNo
Auxiliary CO contacts3
3VA1580-5EF32-0AH0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA1580-5EF32-0AH0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.10 000
Height320 mm
Width210 mm
Depth120 mm
Height (in)12.6 in
Width (in)8.27 in
Depth (in)4.72 in

Product details

It carries 800 A continuously at 40 °C ambient — the full rating holds through 50 °C, then derates to 722 A at 70 °C. That 800 A frame makes it a fit for large feeders, busway taps, or high-current distribution in industrial switchboards. Breaking capacity is the headline: 187 kA at 240 V AC, 121 kA at 415/440 V, 75.6 kA at 500 V, and 52.5 kA at 690 V. Those numbers put it in the high-interrupting category — it handles fault currents from large transformers or utility feeds without needing upstream current-limiting fuses.

Dimensions are 320 mm high, 210 mm wide, 120 mm deep — a standard MCCB footprint for a 3-pole 800 A frame. The auxiliary switch configuration (2 aux + 1 trip alarm) is built in, so no add-on modules are needed for remote status feedback.

Frequently asked questions

Where can I buy 3VA1580-5EF32-0AH0 and how do I get a price?

We source this part to order against an RFQ. Submit a request and we'll confirm availability and current pricing at quote time.

What is the breaking capacity of 3VA1580-5EF32-0AH0 at 240 V?

187 kA at 240 V AC, with 121 kA at 415/440 V, 75.6 kA at 500 V, and 52.5 kA at 690 V.

MPN