Skip to main content
Siemens 3VA1580-5EF32-0DL0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1580-5EF32-0DL0 SENTRON MCCB, 800 A, 3-Pole, 187

MPN3VA1580-5EF32-0DL0

Siemens SENTRON 3VA1580-5EF32-0DL0, molded case circuit breaker, 3-pole, 800 A at 40 °C, interrupting rating 187 kA at 240 V, 121 kA at 415 V, 75.6 kA at 500 V, 52.5 kA at 690 V.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

3VA1580-5EF32-0DL0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Basic switch (supplied) ref.3VA15805EF320AA0
Integrated auxiliary / alarm switch ref.3VA9988-0AB22
3VA1580-5EF32-0DL0 — Ratings
ParameterValue
Number of poles3
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C800 A
Current at 45 °C800 A
Current at 50 °C800 A
Current at 55 °C780 A
Current at 60 °C761 A
Current at 65 °C741 A
Current at 70 °C722 A
Switching capacity classM
Breaking capacity at 240 V187 kA
Breaking capacity at 415 V121 kA
Breaking capacity at 440 V121 kA
Breaking capacity at 500 V75.6 kA
Breaking capacity at 690 V52.5 kA
Power loss, max.242.5 W
3VA1580-5EF32-0DL0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM240
Overcurrent protection functionLI
Ground-fault monitoringWithout
Grounding protection functionNo
3VA1580-5EF32-0DL0 — Construction & Connection
ParameterValue
Main circuit connection typenut keeper kit on both ends
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA1580-5EF32-0DL0 — Accessories & Functions
ParameterValue
Undervoltage releaseYes
Voltage triggerNo
Trip indicatorYes
Communication functionNo
Measurement functionNo
Motor drive optionNo
Auxiliary CO contacts4
3VA1580-5EF32-0DL0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA1580-5EF32-0DL0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.10 000
Height320 mm
Width210 mm
Depth120 mm
Height (in)12.6 in
Width (in)8.27 in
Depth (in)4.72 in

Product details

The Siemens 3VA1580-5EF32-0DL0 is a SENTRON molded case circuit breaker rated 800 A at 40 °C, with full current carry up to 50 °C before derating begins — at 55 °C it holds 780 A, at 70 °C it still delivers 722 A. That thermal curve means this breaker handles high-ambient panels without oversizing the frame, a common pain point in packed switchgear. Interrupting capacity is 187 kA at 240 V, stepping to 121 kA at 415 V and 440 V, 75.6 kA at 500 V, and 52.5 kA at 690 V. For a 3-pole line-protection breaker, those numbers give selectivity headroom downstream — you can coordinate with smaller branch breakers without worrying about cascading faults through the main. That config saves panel-build time — no separate add-on modules to order and snap in.

Dimensions are 320 mm height, 210 mm width, 120 mm depth — a standard MCCB footprint for the 800 A frame class. The 3-pole design with line-protection trip curve fits into a distribution panel or motor control center as a main or large feeder breaker. Rated insulation voltage is 800 V, with operating temperature range from -25 °C to 70 °C and storage from -40 °C to 80 °C. The trip indicator and undervoltage release are factory-integrated, so no field wiring of separate accessories.

Frequently asked questions

Does 3VA1580-5EF32-0DL0 include auxiliary switches and an undervoltage release?

Yes, it ships with 2 auxiliary switches, 1 trip alarm switch, 1 electrical alarm switch, and an undervoltage release — all factory-installed.

MPN
3VA1580-5EF32-0DL0