At 240 V it interrupts 187 kA, dropping to 121 kA at 415 V and 52.5 kA at 690 V — so it handles high-fault scenarios across common industrial voltages without cascading upstream.
Dimensions are 320 mm high × 210 mm wide × 120 mm deep. That depth (120 mm) means it clears most standard gland-plate depths without a sub-panel spacer. Width of 210 mm is the pole-pitch footprint for a 3-pole frame at this rating — verify the existing bus-bar or cable lug layout against the terminal centers before committing the panel layout.
Temperature derating curve
At 55 °C it derates to 780 A, then 761 A at 60 °C, 741 A at 65 °C, and 722 A at 70 °C.
No undervoltage release fitted. No ground-fault monitoring module.