Skip to main content
Siemens 3VA1580-5EF32-0KL0 — Molded Case Circuit Breakers (MCCB)

Siemens SENTRON 3VA1580-5EF32-0KL0 MCCB, 800 A, 3-Pole, 121

MPN3VA1580-5EF32-0KL0

Siemens SENTRON 3VA1580-5EF32-0KL0, molded case circuit breaker, 3-pole, 800 A at 40 °C, 121 kA breaking capacity at 415 V, line protection design.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3VA1580-5EF32-0KL0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Basic switch (supplied) ref.3VA15805EF320AA0
Integrated auxiliary / alarm switch ref.3VA9988-0AB22
3VA1580-5EF32-0KL0 — Ratings
ParameterValue
Number of poles3
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C800 A
Current at 45 °C800 A
Current at 50 °C800 A
Current at 55 °C780 A
Current at 60 °C761 A
Current at 65 °C741 A
Current at 70 °C722 A
Switching capacity classM
Breaking capacity at 240 V187 kA
Breaking capacity at 415 V121 kA
Breaking capacity at 440 V121 kA
Breaking capacity at 500 V75.6 kA
Breaking capacity at 690 V52.5 kA
Power loss, max.240 W
3VA1580-5EF32-0KL0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM240
Overcurrent protection functionLI
Ground-fault monitoringWithout
Grounding protection functionNo
3VA1580-5EF32-0KL0 — Construction & Connection
ParameterValue
Main circuit connection typenut keeper kit on both ends
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA1580-5EF32-0KL0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerYes
Trip indicatorYes
Communication functionNo
Measurement functionNo
Motor drive optionNo
Auxiliary CO contacts4
3VA1580-5EF32-0KL0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA1580-5EF32-0KL0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.10 000
Height320 mm
Width210 mm
Depth120 mm
Height (in)12.6 in
Width (in)8.27 in
Depth (in)4.72 in

Product details

The Siemens SENTRON 3VA1580-5EF32-0KL0 is a 3-pole molded case circuit breaker (MCCB) rated for line protection, carrying 800 A continuously at 40 °C without derating — the same 800 A holds at 45 °C and 50 °C, then steps down to 780 A at 55 °C, 761 A at 60 °C, 741 A at 65 °C, and 722 A at 70 °C, so you size the breaker for the actual panel ambient, not the catalog headline. Breaking capacity hits 187 kA at 240 V, 121 kA at 415 V and 440 V, 75.6 kA at 500 V, and 52.5 kA at 690 V — that 121 kA at 415 V gives solid SCCR headroom for most industrial distribution panels without needing a current-limiting upstream device.

Dimensions: 210 mm wide, 320 mm high, 120 mm deep.

Frequently asked questions

What auxiliary switches come on this MCCB?

It includes 2 auxiliary switches plus 1 trip alarm switch plus 1 electrical alarm switch HQ, plus a shunt trip release (STL).

MPN
3VA1580-5EF32-0KL0