The 4-pole configuration handles three-phase plus neutral switching, common in TN-S or TN-C-S systems where the neutral needs isolation.
Rated breaking capacity reaches 121 kA at 240 V AC, 75.6 kA at 415 V and 440 V, 52.5 kA at 500 V, and 3 kA at 690 V. At a typical 415 V industrial service, 75.6 kA covers most transformer-fed installations up to around 2 MVA. The steep drop to 3 kA at 690 V means this frame is not intended for 690 V main feeders — that's a coordination constraint to flag in the arc-flash study.
The 140 mm width for a 4-pole frame is standard for this class — verify the mounting footprint against the existing backpanel or DIN-rail adapter if retrofitting into a legacy SENTRON or 3VA1 cutout.