Skip to main content
Siemens 3VA2010-5HL32-0CC0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA2010-5HL32-0CC0 SENTRON MCCB, 100 A, 187 kA at 24

MPN3VA2010-5HL32-0CC0

Siemens SENTRON 3VA2 molded case circuit breaker, 3-pole, 100 A, line protection, ETU320 electronic trip unit, 187 kA at 240 V, with undervoltage release and 2 HQ auxiliary switches.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3VA2010-5HL32-0CC0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionLine protection
Basic switch (supplied) ref.3VA2010-5HL32-0AA0
Integrated auxiliary / alarm switch ref.3VA9988-0AA12
3VA2010-5HL32-0CC0 — Ratings
ParameterValue
Number of poles3
Current at 40 °C100 A
Current at 45 °C100 A
Current at 50 °C100 A
Current at 55 °C96.25 A
Current at 60 °C92.5 A
Current at 65 °C88.75 A
Current at 70 °C85 A
Switching capacity classM
Breaking capacity at 240 V187 kA
Breaking capacity at 415 V121 kA
Breaking capacity at 440 V121 kA
Breaking capacity at 500 V79 kA
Breaking capacity at 690 V3.4 kA
Power loss, max.16 W
3VA2010-5HL32-0CC0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU320
3VA2010-5HL32-0CC0 — Construction & Connection
ParameterValue
Main circuit connection typeLug terminal
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA2010-5HL32-0CC0 — Accessories & Functions
ParameterValue
Undervoltage releaseYes
Voltage triggerNo
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts2
3VA2010-5HL32-0CC0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA2010-5HL32-0CC0 — Mechanical
ParameterValue
Height181 mm
Width105 mm
Depth86 mm

Product details

The Siemens 3VA2010-5HL32-0CC0 is a SENTRON 3VA2 molded case circuit breaker (MCCB) rated for 100 A continuous at 40 °C, with an ETU320 electronic trip unit for line protection.

At 415 V and 440 V it holds 121 kA; at 500 V it still delivers 79 kA.

Rated current holds flat at 100 A from 40 °C to 50 °C, then derates linearly to 85 A at 70 °C. In a tightly packed panel with ambient near 60 °C, you lose about 7.5 A — plan your load accordingly.

Integrated auxiliary and undervoltage release

This variant ships with two HQ auxiliary switches (form C) and an undervoltage release (UVR) factory-fitted.

Frequently asked questions

How do I get current pricing and availability for 3VA2010-5HL32-0CC0?

Submit an RFQ through the storefront; pricing and lead time are confirmed at quote time against current distribution stock.

Will 3VA2010-5HL32-0CC0 drop into a panel specified around 3VA1010-2ED32-0JA0 without rewiring?

Yes, both breakers share the same 3VA2 mounting footprint and terminal layout, so it fits without panel modifications.

What is the breaking capacity at 240 V?

187 kA at 240 V AC, which covers high-fault industrial distribution panels.

What compliance documentation does Siemens provide for this MCCB?

Standard Siemens documentation includes RoHS, REACH, and IEC/UL compliance declarations; request them with your RFQ.

MPN
3VA2010-5HL32-0CC0