Skip to main content
Siemens 3VA2010-5HL32-0DA0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA2010-5HL32-0DA0 SENTRON MCCB, 100A, 187kA at 240V

MPN3VA2010-5HL32-0DA0

Siemens SENTRON 3VA2010-5HL32-0DA0, 3-pole molded case circuit breaker, line protection, rated 100 A continuous, 187 kA interrupting at 240 V AC, with undervoltage release.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3VA2010-5HL32-0DA0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionLine protection
Basic switch (supplied) ref.3VA2010-5HL32-0AA0
3VA2010-5HL32-0DA0 — Ratings
ParameterValue
Number of poles3
Current at 40 °C100 A
Current at 45 °C100 A
Current at 50 °C100 A
Current at 55 °C96.25 A
Current at 60 °C92.5 A
Current at 65 °C88.75 A
Current at 70 °C85 A
Switching capacity classM
Breaking capacity at 240 V187 kA
Breaking capacity at 415 V121 kA
Breaking capacity at 440 V121 kA
Breaking capacity at 500 V79 kA
Breaking capacity at 690 V3.4 kA
Power loss, max.16 W
3VA2010-5HL32-0DA0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU320
3VA2010-5HL32-0DA0 — Construction & Connection
ParameterValue
Main circuit connection typeLug terminal
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA2010-5HL32-0DA0 — Accessories & Functions
ParameterValue
Undervoltage releaseYes
Voltage triggerNo
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts0
3VA2010-5HL32-0DA0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA2010-5HL32-0DA0 — Mechanical
ParameterValue
Height181 mm
Width105 mm
Depth86 mm

Product details

MCCB for high-fault panels

Its 100 A continuous rating (Iu) holds at ambient temperatures up to 50 °C without derating; at 55 °C it still carries 96.25 A, and at 70 °C it delivers 85 A — useful for panels with elevated internal heat. At 415/440 V it still breaks 121 kA, and at 690 V it drops to 3.4 kA — so for 690 V systems, verify the available fault current stays under that threshold. The overcurrent release is an ETU320 electronic trip unit, which provides adjustable long-time, short-time, and instantaneous protection curves. No auxiliary contacts, ground-fault monitoring, or communication function are built in; those would need separate add-on modules.

Panel builders should verify the depth clearance for the undervoltage release wiring and any rear-connection terminals.

Frequently asked questions

Who supplies 3VA2010-5HL32-0DA0 and how is it quoted for volume purchases?

This part is supplied through independent distribution channels. It is quoted to order against an RFQ; availability and pricing are confirmed at the time of quote. Volume pricing and scheduled deliveries are available on request.

MPN
3VA2010-5HL32-0DA0