Siemens 3VA2010-5HL32-0JC0 SENTRON MCCB, 100 A, 3-pole

MPN3VA2010-5HL32-0JC0

Siemens SENTRON 3VA2010-5HL32-0JC0, molded case circuit breaker, 3-pole, 100 A continuous, adjustable trip 150–1200 A, 187 kA at 240 V, line protection design, shunt trip release, 2 auxiliary switches HQ.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3VA2010-5HL32-0JC0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Basic switch (supplied) ref.3VA20105HL320AA0
Integrated auxiliary / alarm switch ref.3VA9988-0AA12
3VA2010-5HL32-0JC0 — Ratings
ParameterValue
Number of poles3
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C100 A
Current at 45 °C100 A
Current at 50 °C100 A
Current at 55 °C100 A
Current at 60 °C100 A
Current at 65 °C100 A
Current at 70 °C100 A
Switching capacity classM
Breaking capacity at 240 V187 kA
Breaking capacity at 415 V121 kA
Breaking capacity at 440 V121 kA
Breaking capacity at 500 V75.6 kA
Breaking capacity at 690 V3 kA
Power loss, max.13.5 W
3VA2010-5HL32-0JC0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU320
Overcurrent protection functionLI
Ground-fault monitoringWithout
Grounding protection functionNo
3VA2010-5HL32-0JC0 — Construction & Connection
ParameterValue
Main circuit connection typeon both sides nut keeper kit
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA2010-5HL32-0JC0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerYes
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts2
3VA2010-5HL32-0JC0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA2010-5HL32-0JC0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.25 000
Height181 mm
Width105 mm
Depth86 mm
Height (in)7.13 in
Width (in)4.13 in
Depth (in)3.39 in

Product details

Three poles, rated 100 A continuous from 40 °C up to 70 °C with no derating across that band — that means you can install it in a warm cabinet without recalculating the load schedule. The adjustable thermal-magnetic trip covers 150 A minimum to 1 200 A maximum, so one breaker body covers a wide range of feeder sizes — useful for stocking a single frame across multiple panel builds. Short-circuit ratings hit 187 kA at 240 V, 121 kA at 415 V and 440 V, 75.6 kA at 500 V, and 3 kA at 690 V. Max power loss is 13.5 W, which keeps heat inside a panel manageable.

Dimensions are 86 mm deep, 105 mm wide, 181 mm high — a standard 3-pole MCCB footprint that fits most DIN-rail or panel-mount enclosures. Operating temperature range is -25 °C to 70 °C; storage range is -40 °C to 80 °C.

Frequently asked questions

What are the key ratings for 3VA2010-5HL32-0JC0?

100 A continuous at 40–70 °C, adjustable trip 150–1 200 A, 3-pole, 187 kA SCCR at 240 V, 121 kA at 415/440 V, 75.6 kA at 500 V, 3 kA at 690 V. Includes shunt trip and 2 auxiliary switches.

Where can I buy 3VA2010-5HL32-0JC0?

Sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — send your quantity and target delivery window for a firm offer.

What is the physical size of 3VA2010-5HL32-0JC0?

86 mm deep, 105 mm wide, 181 mm high — a standard 3-pole MCCB footprint for panel-mount or DIN-rail enclosures.