Siemens SENTRON 3VA2010-5HL32-0JH0 — 100 A MCCB for Line Protection
It carries a maximum breaking capacity of 187 kA at 240 V AC, stepping down to 121 kA at 415/440 V, 75.6 kA at 500 V, and 3 kA at 690 V — the voltage-dependent curve that governs fault clearing in your system.
Power loss is 13.5 W maximum at rated current — a figure to account for in enclosed panel thermal calculations, especially when grouping multiple breakers.
Auxiliary and Release Configuration
The trip indicator and voltage trigger are present; undervoltage release is not included on this order code. No ground-fault monitoring or communication function is fitted.
The depth of 86 mm (3.39 in) fits most shallow enclosures; verify clearance for the shunt trip wiring and auxiliary switch connections.