Line protection MCCB with ETU320 — 100 A, 187 kA SCCR
The front face is IP40-rated — suitable for enclosure mounting behind a panel door, not for washdown exposure. Mechanical endurance is rated at 20,000 cycles.

Siemens SENTRON 3VA2 molded case circuit breaker, 3-pole, 100 A, 187 kA at 240 V, ETU320 electronic trip unit, IP40 front, 86 mm depth.
| Parameter | Value |
|---|---|
| Product designation | Molded case circuit breaker |
| Brand / range | SENTRON |
| Product version | Line protection |
| Basic switch (supplied) ref. | 3VA2010-5HL36-0AA0 |
| Integrated auxiliary / alarm switch ref. | 3VA9988-0AA11 |
| Parameter | Value |
|---|---|
| Number of poles | 3 |
| Current at 40 °C | 100 A |
| Current at 45 °C | 100 A |
| Current at 50 °C | 100 A |
| Current at 55 °C | 96.25 A |
| Current at 60 °C | 92.5 A |
| Current at 65 °C | 88.75 A |
| Current at 70 °C | 85 A |
| Switching capacity class | M |
| Breaking capacity at 240 V | 187 kA |
| Breaking capacity at 415 V | 121 kA |
| Breaking capacity at 440 V | 121 kA |
| Breaking capacity at 500 V | 79 kA |
| Breaking capacity at 690 V | 3.4 kA |
| Power loss, max. | 13.5 W |
| Parameter | Value |
|---|---|
| Overcurrent release (trip unit) type | ETU320 |
| Parameter | Value |
|---|---|
| Main circuit connection type | box terminal |
| Main circuit connector arrangement | Front terminal |
| Protection class (IP), front | IP40 |
| Parameter | Value |
|---|---|
| Undervoltage release | No |
| Voltage trigger | No |
| Trip indicator | No |
| Communication function | No |
| Measurement function | No |
| Motor drive option | Yes |
| Auxiliary CO contacts | 2 |
| Parameter | Value |
|---|---|
| Operating temperature, max. | 70 °C |
| Operating temperature, min. | -25 °C |
| Storage temperature, max. | 80 °C |
| Storage temperature, min. | -40 °C |
| Parameter | Value |
|---|---|
| Height | 181 mm |
| Width | 105 mm |
| Depth | 86 mm |
The front face is IP40-rated — suitable for enclosure mounting behind a panel door, not for washdown exposure. Mechanical endurance is rated at 20,000 cycles.
This part is available to order through independent distribution. Submit an RFQ for current availability and pricing — stock and lead time are confirmed at quote time.
Rated continuous current Iu is 100 A, interrupting capacity is 187 kA at 240 V (121 kA at 415/440 V, 79 kA at 500 V, 3.4 kA at 690 V). It is a 3-pole molded case circuit breaker with ETU320 electronic trip unit, 800 V rated insulation voltage, and IP40 front protection.
No. This variant has no trip indicator, no undervoltage release, no communication function, no phase-failure detection, no ground-fault monitoring, and no auxiliary release. It ships with two HP auxiliary switches only.
No related articles