Siemens 3VA2010-5HL36-0AJ0 SENTRON MCCB, 100 A, 3-Pole, 187

MPN3VA2010-5HL36-0AJ0

Siemens SENTRON 3VA2010-5HL36-0AJ0, molded case circuit breaker, 3-pole, 100 A continuous, 187 kA breaking at 240 V, line protection design.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

3VA2010-5HL36-0AJ0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Basic switch (supplied) ref.3VA20105HL360AA0
Integrated auxiliary / alarm switch ref.3VA9988-0AB11

Ratings

3VA2010-5HL36-0AJ0 — Ratings
ParameterValue
Number of poles3
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C100 A
Current at 45 °C100 A
Current at 50 °C100 A
Current at 55 °C100 A
Current at 60 °C100 A
Current at 65 °C100 A
Current at 70 °C100 A
Switching capacity classM
Breaking capacity at 240 V187 kA
Breaking capacity at 415 V121 kA
Breaking capacity at 440 V121 kA
Breaking capacity at 500 V75.6 kA
Breaking capacity at 690 V3 kA
Power loss, max.13.5 W

Protection & Trip Unit

3VA2010-5HL36-0AJ0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU320
Overcurrent protection functionLI
Ground-fault monitoringWithout
Grounding protection functionNo

Construction & Connection

3VA2010-5HL36-0AJ0 — Construction & Connection
ParameterValue
Main circuit connection typedouble-sided box terminal
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40

Accessories & Functions

3VA2010-5HL36-0AJ0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerNo
Trip indicatorYes
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts3

Environmental

3VA2010-5HL36-0AJ0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C

Mechanical

3VA2010-5HL36-0AJ0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.25 000
Height181 mm
Width105 mm
Depth86 mm
Height (in)7.13 in
Width (in)4.13 in
Depth (in)3.39 in

Product details

The Siemens SENTRON 3VA2010-5HL36-0AJ0 is a 3-pole molded case circuit breaker rated for 100 A continuous current, with a maximum breaking capacity of 187 kA at 240 V AC. It is designed for line protection in industrial distribution panels, with no ground-fault monitoring or undervoltage release built in.

Breaking capacity and selectivity

At 240 V the breaker interrupts 187 kA; at 415 V and 440 V that drops to 121 kA, then 75.6 kA at 500 V, and 3 kA at 690 V. For a 100 A feed, the 187 kA figure at 240 V gives substantial headroom for high-fault utility feeds or transformer secondaries — selectivity coordination downstream is straightforward because the upstream device clears fast without nuisance tripping. The 100 A rating holds flat across the full ambient range from 40 °C to 70 °C — no derating needed in a warm enclosure or near other heat sources.

Mounting and panel fit

Dimensions are 105 mm wide, 181 mm tall, 86 mm deep. The 86 mm depth fits standard MCCB mounting plates and leaves room for rear-connected busbars or cable lugs without forcing a deeper enclosure. The auxiliary switch block is factory-configured as 2 auxiliary switches plus 1 trip alarm switch (HP type). No communication module or voltage-trip accessory is included — this is a straight line-protection breaker with local indication only.

Frequently asked questions

Where can I buy 3VA2010-5HL36-0AJ0 and how do I get a price?

This part is sourced to order against an RFQ through independent distribution. Submit an RFQ for current availability and pricing — confirmed at quote time.

What is 3VA2010-5HL36-0AJ0's listed depth?

The depth is 86 mm (3.39 in).

What is 3VA2010-5HL36-0AJ0's listed width?

The width is 105 mm (4.13 in).

Will 3VA2010-5HL36-0AJ0 drop into a panel specified around 5SQ2370-2YA05 without rewiring?

Both are 3-pole MCCBs in the 100 A class, but the 5SQ2370-2YA05 is a different manufacturer's design with different mounting footprint and terminal layout. Panel fit and busbar alignment must be verified — they are not drop-in interchangeable without rewiring.

MPN