Siemens 3VA2010-5HL36-0CH0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA2010-5HL36-0CH0 SENTRON MCCB, 100 A, 3-pole, line

MPN3VA2010-5HL36-0CH0

Siemens SENTRON 3VA2010-5HL36-0CH0, molded case circuit breaker, 3-pole, 100 A, line protection, with undervoltage release and auxiliary switches.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

3VA2010-5HL36-0CH0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Basic switch (supplied) ref.3VA20105HL360AA0
Integrated auxiliary / alarm switch ref.3VA9988-0AB12

Ratings

3VA2010-5HL36-0CH0 — Ratings
ParameterValue
Number of poles3
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C100 A
Current at 45 °C100 A
Current at 50 °C100 A
Current at 55 °C100 A
Current at 60 °C100 A
Current at 65 °C100 A
Current at 70 °C100 A
Switching capacity classM
Breaking capacity at 240 V187 kA
Breaking capacity at 415 V121 kA
Breaking capacity at 440 V121 kA
Breaking capacity at 500 V75.6 kA
Breaking capacity at 690 V3 kA
Power loss, max.16 W

Protection & Trip Unit

3VA2010-5HL36-0CH0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU320
Overcurrent protection functionLI
Ground-fault monitoringWithout
Grounding protection functionNo

Construction & Connection

3VA2010-5HL36-0CH0 — Construction & Connection
ParameterValue
Main circuit connection typedouble-sided box terminal
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40

Accessories & Functions

3VA2010-5HL36-0CH0 — Accessories & Functions
ParameterValue
Undervoltage releaseYes
Voltage triggerNo
Trip indicatorYes
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts3

Environmental

3VA2010-5HL36-0CH0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C

Mechanical

3VA2010-5HL36-0CH0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.25 000
Height181 mm
Width105 mm
Depth86 mm
Height (in)7.13 in
Width (in)4.13 in
Depth (in)3.39 in

Product details

What this MCCB does on the line

The Siemens 3VA2010-5HL36-0CH0 is a SENTRON molded case circuit breaker rated for 100 A continuous current across the full ambient range from 40 °C to 70 °C — no derating needed as the panel warms up near the press. Its 187 kA interrupting capacity at 240 V gives you fault-clearing headroom for high-available-fault-current distribution, while the 3-pole design handles three-phase loads common in industrial ovens and curing lines.

Breaking capacity across voltage levels

The interrupting rating drops as system voltage rises: 187 kA at 240 V, 121 kA at 415 V and 440 V, 75.6 kA at 500 V, and 3 kA at 690 V. For a 480 V panel feeding a curing press, the 75.6 kA figure is the one that governs SCCR coordination with upstream gear.

Mounting dimensions and panel fit

At 86 mm deep, 105 mm wide, and 181 mm tall, this breaker fits standard SENTRON 3VA mounting footprints. The 3-pole width of 105 mm matches the common panel cutout for 100 A frame MCCBs.

MPN
3VA2010-5HL36-0CH0