The Siemens 3VA2010-5HL36-0DA0 is a SENTRON 3VA2 molded case circuit breaker (MCCB) rated for 100 A continuous current, verified across the full operating temperature range from -25 °C to 70 °C with no derating — the 100 A holds at every 5 °C increment per the spec table. That means this breaker delivers its full nameplate rating in a warm panel without needing to oversize for ambient conditions. Breaking capacity is voltage-dependent: 187 kA at 240 V, 121 kA at 415 V and 440 V, 75.6 kA at 500 V, and 3 kA at 690 V.

Siemens 3VA2010-5HL36-0DA0 SENTRON MCCB, 100 A, 3-Pole, UVR
Siemens SENTRON 3VA2 molded case circuit breaker, 3VA2010-5HL36-0DA0, 3-pole, 100 A continuous rating, line protection design, with integrated undervoltage release (UVR).
Specifications
| Parameter | Value |
|---|---|
| Product designation | Molded case circuit breaker |
| Brand / range | SENTRON |
| Basic switch (supplied) ref. | 3VA20105HL360AA0 |
| Parameter | Value |
|---|---|
| Number of poles | 3 |
| Rated operational voltage Ue (AC) | 690 V |
| Rated insulation voltage Ui | 800 V |
| Current at 40 °C | 100 A |
| Current at 45 °C | 100 A |
| Current at 50 °C | 100 A |
| Current at 55 °C | 100 A |
| Current at 60 °C | 100 A |
| Current at 65 °C | 100 A |
| Current at 70 °C | 100 A |
| Switching capacity class | M |
| Breaking capacity at 240 V | 187 kA |
| Breaking capacity at 415 V | 121 kA |
| Breaking capacity at 440 V | 121 kA |
| Breaking capacity at 500 V | 75.6 kA |
| Breaking capacity at 690 V | 3 kA |
| Power loss, max. | 16 W |
| Parameter | Value |
|---|---|
| Overcurrent release (trip unit) type | ETU320 |
| Overcurrent protection function | LI |
| Ground-fault monitoring | Without |
| Grounding protection function | No |
| Parameter | Value |
|---|---|
| Main circuit connection type | double-sided box terminal |
| Main circuit connector arrangement | Front terminal |
| Protection class (IP), front | IP40 |
| Parameter | Value |
|---|---|
| Undervoltage release | Yes |
| Voltage trigger | No |
| Trip indicator | No |
| Communication function | No |
| Measurement function | No |
| Motor drive option | Yes |
| Auxiliary CO contacts | 0 |
| Parameter | Value |
|---|---|
| Operating temperature, max. | 70 °C |
| Operating temperature, min. | -25 °C |
| Storage temperature, max. | 80 °C |
| Storage temperature, min. | -40 °C |
| Parameter | Value |
|---|---|
| Mechanical service life (operating cycles), typ. | 25 000 |
| Height | 181 mm |
| Width | 105 mm |
| Depth | 86 mm |
| Height (in) | 7.13 in |
| Width (in) | 4.13 in |
| Depth (in) | 3.39 in |
Product details
Frequently asked questions
What is the continuous current rating of this MCCB?
The continuous current rating is 100 A, and it holds that value across the entire operating temperature range from -25 °C to 70 °C with no derating required.
Does this breaker include an undervoltage release?
Yes, the 3VA2010-5HL36-0DA0 includes an integrated undervoltage release (UVR) as the auxiliary release.