Siemens 3VA2010-5HL42-0AA0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA2010-5HL42-0AA0 SENTRON MCCB, 100A, 4-Pole, ETU32

MPN3VA2010-5HL42-0AA0
Active

Siemens SENTRON 3VA series, molded case circuit breaker, 3VA2010-5HL42-0AA0, 100 A, 4-pole, ETU320 electronic trip unit, line protection, breaking capacity 187 kA at 240 V AC.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3VA2010-5HL42-0AA0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionLine protection
3VA2010-5HL42-0AA0 — Ratings
ParameterValue
Number of poles4
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C100 A
Current at 45 °C100 A
Current at 50 °C100 A
Current at 55 °C100 A
Current at 60 °C100 A
Current at 65 °C100 A
Current at 70 °C100 A
Switching capacity classM
Breaking capacity at 240 V187 kA
Breaking capacity at 415 V121 kA
Breaking capacity at 440 V121 kA
Breaking capacity at 500 V75.6 kA
Breaking capacity at 690 V3 kA
Power loss, max.13.5 W
3VA2010-5HL42-0AA0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU320
Overcurrent protection functionLI
Ground-fault monitoringWithout
3VA2010-5HL42-0AA0 — Construction & Connection
ParameterValue
Main circuit connection typeon both sides nut keeper kit
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA2010-5HL42-0AA0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerNo
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts0
3VA2010-5HL42-0AA0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA2010-5HL42-0AA0 — Mechanical
ParameterValue
Height181 mm
Width140 mm
Depth86 mm
Height (in)7.13 in
Width (in)5.51 in
Depth (in)3.39 in

Product details

The Siemens SENTRON 3VA2010-5HL42-0AA0 is a 4-pole molded case circuit breaker (MCCB) rated for 100 A continuous current across its entire operating temperature range — from 40 °C through 70 °C, the current rating holds flat at 100 A, no derating needed in a warm enclosure. Breaking capacity is the real story here: 187 kA at 240 V AC, 121 kA at 415 V and 440 V, 75.6 kA at 500 V, and 3 kA at 690 V. This is a straightforward feeder or main breaker for a distribution panel.

Keep it inside the panel, not on the door.

Power loss and thermal considerations

Maximum power loss is 13.5 W. In a densely packed panel, that heat adds up — account for it in the enclosure's thermal budget.

Frequently asked questions

Where can I buy 3VA2010-5HL42-0AA0 and how do I get a price?

This part is sourced to order against an RFQ through independent distribution. Submit a request for quote; availability and current pricing are confirmed at quote time.

What is the breaking capacity of 3VA2010-5HL42-0AA0 at different voltages?

Breaking capacity is 187 kA at 240 V AC, 121 kA at 415 V and 440 V, 75.6 kA at 500 V, and 3 kA at 690 V AC.

Does 3VA2010-5HL42-0AA0 have adjustable neutral protection?

Yes, the N-conductor protection is adjustable to OFF, 50%, or 100% of the phase current.

MPN
3VA2010-5HL42-0AA0