Skip to main content
Siemens 3VA2010-5HM42-0AA0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA2010-5HM42-0AA0 SENTRON MCCB, 4P, 100 A, ETU330

MPN3VA2010-5HM42-0AA0
Active

Siemens SENTRON 3VA2010-5HM42-0AA0, 4-pole molded case circuit breaker, 100 A continuous, ETU330 electronic trip unit, line protection version.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

3VA2010-5HM42-0AA0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionLine protection

Ratings

3VA2010-5HM42-0AA0 — Ratings
ParameterValue
Number of poles4
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C100 A
Current at 45 °C100 A
Current at 50 °C100 A
Current at 55 °C100 A
Current at 60 °C100 A
Current at 65 °C100 A
Current at 70 °C100 A
Switching capacity classM
Breaking capacity at 240 V187 kA
Breaking capacity at 415 V121 kA
Breaking capacity at 440 V121 kA
Breaking capacity at 500 V75.6 kA
Breaking capacity at 690 V3 kA
Power loss, max.13.5 W

Protection & Trip Unit

3VA2010-5HM42-0AA0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU330
Overcurrent protection functionLIG
Ground-fault monitoringSummation current formation L + N conductor

Construction & Connection

3VA2010-5HM42-0AA0 — Construction & Connection
ParameterValue
Main circuit connection typeon both sides nut keeper kit
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40

Accessories & Functions

3VA2010-5HM42-0AA0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerNo
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts0

Environmental

3VA2010-5HM42-0AA0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C

Mechanical

3VA2010-5HM42-0AA0 — Mechanical
ParameterValue
Height181 mm
Width140 mm
Depth86 mm
Height (in)7.13 in
Width (in)5.51 in
Depth (in)3.39 in

Product details

What the ratings mean for fit

The Siemens SENTRON 3VA2010-5HM42-0AA0 is a 4-pole molded case circuit breaker rated for 100 A continuous current across the full ambient range from 40 °C to 70 °C — no derating required up to that ceiling. The interrupting ratings are what drive the panel coordination: 187 kA at 240 V AC, 121 kA at 415 V and 440 V, 75.6 kA at 500 V, and 3 kA at 690 V. These are the SCCR values the breaker can safely clear under fault without upstream cascading, so the 240 V and 415 V figures are the ones that govern for most North American and European distribution panels. The ETU330 electronic trip unit provides adjustable long-time, short-time, instantaneous, and ground-fault protection; the N-conductor protection is field-configurable to OFF, 50%, or 100% of the phase rating. Rated insulation voltage is 800 V, and the maximum operating voltage is 690 V AC. Power loss at rated current is 13.5 W maximum — relevant for thermal budgeting inside a sealed or tightly packed enclosure. The front face carries IP40 protection, so the breaker is suitable for general indoor panel installation where no water jets are present.

Integration and deployment context

The breaker measures 86 mm deep, 140 mm wide, and 181 mm high. The 4-pole footprint matches standard Siemens 3VA panel mounting; the 140 mm width is the same as the 3-pole variant's width plus one additional pole module. Ground-fault monitoring is implemented via summation current formation on the L + N conductors — a single core-balance CT approach that does not require a separate GFCI module.

Frequently asked questions

Where can I buy 3VA2010-5HM42-0AA0?

This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time.

What are the interrupting ratings for 3VA2010-5HM42-0AA0?

187 kA at 240 V AC, 121 kA at 415 V and 440 V AC, 75.6 kA at 500 V AC, and 3 kA at 690 V AC.

What is the continuous current rating and does it derate with temperature?

100 A continuous from 40 °C through 70 °C ambient — no derating required across that range.

What electronic trip unit does this breaker use?

The ETU330 electronic trip unit, which provides adjustable long-time, short-time, instantaneous, and ground-fault protection. N-conductor protection is configurable to OFF, 50%, or 100% of the phase rating.

MPN