It carries an interrupting capacity of 187 kA at 240 V, 121 kA at 415/440 V, 79 kA at 500 V, and 3.4 kA at 690 V — so the SCCR headroom at typical 400 V distribution levels is generous for most industrial panel designs.
Above that it derates linearly: 96.25 A at 55 °C, 92.5 A at 60 °C, 88.75 A at 65 °C, and 85 A at 70 °C. If your enclosure runs hot — say next to a VFD or transformer — factor that curve into the load schedule rather than oversizing the frame.
Feature set and release configuration
Two auxiliary switches (HQ type) are included for status feedback.