The Siemens SENTRON 3VA2010-5HN32-0DL0 is a 3-pole molded case circuit breaker rated for 100 A continuous current with no derating across the full 40 °C to 70 °C operating range — meaning you can load it to nameplate in a warm enclosure without bumping the frame size. That gives the panel builder direct status feedback without adding external relays. Designed for line protection, this MCCB has a trip indicator and no communication function — it is a standalone overcurrent protector, not a smart breaker.

Siemens 3VA2010-5HN32-0DL0 SENTRON MCCB, 100 A, 3-Pole, 187
Siemens SENTRON 3VA2010-5HN32-0DL0, molded case circuit breaker, 3-pole, 100 A continuous, 187 kA interrupting at 240 V, line protection design with undervoltage release.
Specifications
| Parameter | Value |
|---|---|
| Product designation | Molded case circuit breaker |
| Brand / range | SENTRON |
| Basic switch (supplied) ref. | 3VA20105HN320AA0 |
| Integrated auxiliary / alarm switch ref. | 3VA9988-0AB22 |
| Parameter | Value |
|---|---|
| Number of poles | 3 |
| Rated operational voltage Ue (AC) | 690 V |
| Rated insulation voltage Ui | 800 V |
| Current at 40 °C | 100 A |
| Current at 45 °C | 100 A |
| Current at 50 °C | 100 A |
| Current at 55 °C | 100 A |
| Current at 60 °C | 100 A |
| Current at 65 °C | 100 A |
| Current at 70 °C | 100 A |
| Switching capacity class | M |
| Breaking capacity at 240 V | 187 kA |
| Breaking capacity at 415 V | 121 kA |
| Breaking capacity at 440 V | 121 kA |
| Breaking capacity at 500 V | 75.6 kA |
| Breaking capacity at 690 V | 3 kA |
| Power loss, max. | 16 W |
| Parameter | Value |
|---|---|
| Overcurrent release (trip unit) type | ETU350 |
| Overcurrent protection function | LSI |
| Ground-fault monitoring | Without |
| Grounding protection function | No |
| Parameter | Value |
|---|---|
| Main circuit connection type | on both sides nut keeper kit |
| Main circuit connector arrangement | Front terminal |
| Protection class (IP), front | IP40 |
| Parameter | Value |
|---|---|
| Undervoltage release | Yes |
| Voltage trigger | No |
| Trip indicator | Yes |
| Communication function | No |
| Measurement function | No |
| Motor drive option | Yes |
| Auxiliary CO contacts | 4 |
| Parameter | Value |
|---|---|
| Operating temperature, max. | 70 °C |
| Operating temperature, min. | -25 °C |
| Storage temperature, max. | 80 °C |
| Storage temperature, min. | -40 °C |
| Parameter | Value |
|---|---|
| Mechanical service life (operating cycles), typ. | 25 000 |
| Height | 181 mm |
| Width | 105 mm |
| Depth | 86 mm |
| Height (in) | 7.13 in |
| Width (in) | 4.13 in |
| Depth (in) | 3.39 in |
Product details
Frequently asked questions
What is the physical size of this MCCB?
Width 105 mm, height 181 mm, depth 86 mm. It fits the standard SENTRON 3VA frame footprint.
Does this breaker include an undervoltage release?
Yes, it ships with an undervoltage release (UVR) plus 2 auxiliary switches, 1 trip alarm switch, and 1 electrical alarm switch HQ.