The SENTRON 3VA2010-5HN32-0JH0 is a 3-pole molded case circuit breaker rated for 100 A continuous current at 40 °C through 70 °C — no derating needed across that band, which simplifies panel build in warm enclosures. Interrupting capacity hits 187 kA at 240 V, 121 kA at 415/440 V, and 75.6 kA at 500 V; at 690 V it still clears 3 kA. That covers most industrial service-entrance and feeder applications without needing a current-limiting upstream device.
Auxiliary and release configuration
Factory-fitted with 2 auxiliary switches plus 1 trip alarm switch (HQ designation) and a shunt trip release (STL). That means you get remote status indication and a remote-trip capability without adding aftermarket kits — one less SKU to track. The shunt trip lets you integrate with emergency-stop circuits or PLC-driven trip commands.
Panel fit
Footprint is 105 mm wide, 181 mm tall, 86 mm deep — standard 3-pole MCCB spacing for DIN-rail or panel-mount installation. Power loss is 13.5 W maximum, so ventilation planning is straightforward in a typical enclosure.