Skip to main content
Siemens 3VA2010-5HN36-0AJ0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA2010-5HN36-0AJ0 SENTRON MCCB, 100 A, 3-Pole, 187

MPN3VA2010-5HN36-0AJ0

Siemens SENTRON 3VA2010-5HN36-0AJ0, molded case circuit breaker, 3-pole, 100 A rated continuous current, 187 kA breaking capacity at 240 VAC, line protection design.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3VA2010-5HN36-0AJ0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Basic switch (supplied) ref.3VA20105HN360AA0
Integrated auxiliary / alarm switch ref.3VA9988-0AB11
3VA2010-5HN36-0AJ0 — Ratings
ParameterValue
Number of poles3
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C100 A
Current at 45 °C100 A
Current at 50 °C100 A
Current at 55 °C100 A
Current at 60 °C100 A
Current at 65 °C100 A
Current at 70 °C100 A
Switching capacity classM
Breaking capacity at 240 V187 kA
Breaking capacity at 415 V121 kA
Breaking capacity at 440 V121 kA
Breaking capacity at 500 V75.6 kA
Breaking capacity at 690 V3 kA
Power loss, max.13.5 W
3VA2010-5HN36-0AJ0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU350
Overcurrent protection functionLSI
Ground-fault monitoringWithout
Grounding protection functionNo
3VA2010-5HN36-0AJ0 — Construction & Connection
ParameterValue
Main circuit connection typedouble-sided box terminal
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA2010-5HN36-0AJ0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerNo
Trip indicatorYes
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts3
3VA2010-5HN36-0AJ0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA2010-5HN36-0AJ0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.25 000
Height181 mm
Width105 mm
Depth86 mm
Height (in)7.13 in
Width (in)4.13 in
Depth (in)3.39 in

Product details

The Siemens SENTRON 3VA2010-5HN36-0AJ0 is a 3-pole molded case circuit breaker (MCCB) rated for 100 A continuous current at 40 °C through 70 °C, with no derating across that ambient span — a clean 100 A at every temperature point the datasheet lists. Breaking capacity is 187 kA at 240 V, 121 kA at 415 V and 440 V, 75.6 kA at 500 V, and 3 kA at 690 V — the 690 V figure is the one to watch if your system runs at that level; it drops sharply from the 500 V rating. Design is line protection, meaning it's intended for feeder and main breaker duty rather than motor branch-circuit protection (which would require a different trip curve or a motor-protective breaker).

Physical footprint: 86 mm depth, 105 mm width, 181 mm height.

Auxiliary and alarm switching

The auxiliary switches signal the open/closed position of the breaker; the trip alarm switch indicates that the breaker has tripped on fault, not just been manually opened.

The base switch part number is 3VA20105HN360AA0 — the -0AJ0 suffix denotes the specific auxiliary switch and trip alarm configuration. If your BOM calls for the exact -0AJ0 variant, the auxiliary switch complement is the distinguishing feature.

Frequently asked questions

What is the breaking capacity of this MCCB at 415 V?

121 kA at 415 VAC, which is the same rating as at 440 V. The capacity drops to 75.6 kA at 500 V and to 3 kA at 690 V.

Where can I buy the 3VA2010-5HN36-0AJ0 and how is it quoted?

This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm price and lead time.

Does this breaker include auxiliary switches or a shunt trip?

It includes 2 auxiliary switches plus 1 trip alarm switch (HP type). It does not include an undervoltage release, ground-fault monitoring, or communication function.

What are the physical dimensions of the 3VA2010-5HN36-0AJ0?

Depth is 86 mm, width is 105 mm, height is 181 mm. The 105 mm width is the key dimension for panel spacing on a 3-pole breaker.

MPN
3VA2010-5HN36-0AJ0