Skip to main content
Siemens 3VA2010-5HN36-0HA0 — Molded Case Circuit Breakers (MCCB)

SENTRON 3VA2010-5HN36-0HA0 MCCB, 100 A, 3-Pole, Shunt Trip

MPN3VA2010-5HN36-0HA0

SENTRON 3VA2010-5HN36-0HA0, molded case circuit breaker, 3-pole, 100 A, 187 kA at 240 V, shunt trip release, line protection design.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

3VA2010-5HN36-0HA0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Basic switch (supplied) ref.3VA20105HN360AA0

Ratings

3VA2010-5HN36-0HA0 — Ratings
ParameterValue
Number of poles3
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C100 A
Current at 45 °C100 A
Current at 50 °C100 A
Current at 55 °C100 A
Current at 60 °C100 A
Current at 65 °C100 A
Current at 70 °C100 A
Switching capacity classM
Breaking capacity at 240 V187 kA
Breaking capacity at 415 V121 kA
Breaking capacity at 440 V121 kA
Breaking capacity at 500 V75.6 kA
Breaking capacity at 690 V3 kA
Power loss, max.13.5 W

Protection & Trip Unit

3VA2010-5HN36-0HA0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU350
Overcurrent protection functionLSI
Ground-fault monitoringWithout
Grounding protection functionNo

Construction & Connection

3VA2010-5HN36-0HA0 — Construction & Connection
ParameterValue
Main circuit connection typedouble-sided box terminal
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40

Accessories & Functions

3VA2010-5HN36-0HA0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerYes
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts0

Environmental

3VA2010-5HN36-0HA0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C

Mechanical

3VA2010-5HN36-0HA0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.25 000
Height181 mm
Width105 mm
Depth86 mm
Height (in)7.13 in
Width (in)4.13 in
Depth (in)3.39 in

Product details

The SENTRON 3VA2010-5HN36-0HA0 is a 3-pole molded case circuit breaker rated for 100 A continuous current, with a shunt trip release (STL) for remote tripping. It's designed for line protection in distribution panels, sized at 86 mm deep by 105 mm wide by 181 mm tall — a standard footprint that fits most 3-pole MCCB mounting slots without re-drilling the backplate.

Interrupting capacity and selectivity

Rated interrupting capacity hits 187 kA at 240 V, dropping to 121 kA at 415 V and 440 V, then 75.6 kA at 500 V, and 3 kA at 690 V. That 187 kA at 240 V means this breaker can clear a bolted fault on a 240 V secondary bus without upstream fuses needing to open — useful for high-fault panels near large transformers. The 100 A frame holds its rating flat from 40 °C through 70 °C ambient, so no derating curve to calculate in a warm enclosure.

Shunt trip and auxiliary release

The shunt trip (STL) release allows a remote signal — from an E-stop, fire alarm relay, or PLC digital output — to trip the breaker without an operator at the panel. No undervoltage release on this variant, so it won't drop out on a brownout; the shunt trip is a separate voltage-trigger input that needs a sustained signal to hold the trip coil energized.

Frequently asked questions

Where can I buy 3VA2010-5HN36-0HA0 and get a price?

Sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm price and lead time.

What are the key ratings of 3VA2010-5HN36-0HA0?

100 A continuous current, 3-pole, interrupting capacity of 187 kA at 240 V, 121 kA at 415 V, 75.6 kA at 500 V, and 3 kA at 690 V. Includes a shunt trip release for remote tripping.

What are the mounting dimensions for this MCCB?

86 mm deep, 105 mm wide, 181 mm tall — a standard 3-pole MCCB footprint that fits most panel backplates without modification.

MPN
3VA2010-5HN36-0HA0