The Siemens SENTRON 3VA2010-5HN36-0KC0 is a 3-pole molded case circuit breaker rated for 100 A continuous current across the full ambient range from 40 °C to 70 °C — no derating needed up to the enclosure's thermal limit. Its interrupting capacity reaches 187 kA at 240 V AC, 121 kA at 415/440 V, 75.6 kA at 500 V, and 3 kA at 690 V, covering high-fault service-entrance and distribution applications where SCCR headroom is critical for selectivity coordination. The 13.5 W maximum power loss stays manageable for standard panel layouts.

Siemens 3VA2010-5HN36-0KC0 SENTRON MCCB, 100 A, 3-Pole, 187
Siemens SENTRON 3VA2010-5HN36-0KC0, molded case circuit breaker, 3-pole, 100 A continuous rating, 187 kA interrupting at 240 V AC, line protection design with shunt trip and auxiliary switches.
Specifications
| Parameter | Value |
|---|---|
| Product designation | Molded case circuit breaker |
| Brand / range | SENTRON |
| Basic switch (supplied) ref. | 3VA20105HN360AA0 |
| Integrated auxiliary / alarm switch ref. | 3VA9988-0AA12 |
| Parameter | Value |
|---|---|
| Number of poles | 3 |
| Rated operational voltage Ue (AC) | 690 V |
| Rated insulation voltage Ui | 800 V |
| Current at 40 °C | 100 A |
| Current at 45 °C | 100 A |
| Current at 50 °C | 100 A |
| Current at 55 °C | 100 A |
| Current at 60 °C | 100 A |
| Current at 65 °C | 100 A |
| Current at 70 °C | 100 A |
| Switching capacity class | M |
| Breaking capacity at 240 V | 187 kA |
| Breaking capacity at 415 V | 121 kA |
| Breaking capacity at 440 V | 121 kA |
| Breaking capacity at 500 V | 75.6 kA |
| Breaking capacity at 690 V | 3 kA |
| Power loss, max. | 13.5 W |
| Parameter | Value |
|---|---|
| Overcurrent release (trip unit) type | ETU350 |
| Overcurrent protection function | LSI |
| Ground-fault monitoring | Without |
| Grounding protection function | No |
| Parameter | Value |
|---|---|
| Main circuit connection type | double-sided box terminal |
| Main circuit connector arrangement | Front terminal |
| Protection class (IP), front | IP40 |
| Parameter | Value |
|---|---|
| Undervoltage release | No |
| Voltage trigger | Yes |
| Trip indicator | No |
| Communication function | No |
| Measurement function | No |
| Motor drive option | Yes |
| Auxiliary CO contacts | 2 |
| Parameter | Value |
|---|---|
| Operating temperature, max. | 70 °C |
| Operating temperature, min. | -25 °C |
| Storage temperature, max. | 80 °C |
| Storage temperature, min. | -40 °C |
| Parameter | Value |
|---|---|
| Mechanical service life (operating cycles), typ. | 25 000 |
| Height | 181 mm |
| Width | 105 mm |
| Depth | 86 mm |
| Height (in) | 7.13 in |
| Width (in) | 4.13 in |
| Depth (in) | 3.39 in |
Product details
Frequently asked questions
What is the interrupting capacity of 3VA2010-5HN36-0KC0 at 240 V?
187 kA at 240 V AC, dropping to 121 kA at 415/440 V, 75.6 kA at 500 V, and 3 kA at 690 V.
Where can I buy 3VA2010-5HN36-0KC0?
Sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing confirmed at quote time.